Goodrive350-19 series VFD Function parameter list
- 376 -
Function
code
Name
Description
Default
value
Modify
limit
P92.25
Enabling
PT100/PT1000
disconnection
detection
0x00
–0x11
Ones place: PT100 disconnection detection
0: Disable
1: Enable
Tens place: PT1000 disconnection detection
0: Disable
1: Enable
0x00
○
P92.26
Enabling digital of
PT100/PT1000
calibration
temperature
0
–4
0: Invalid
1: Enable PT100 calibration lower limit digital
2: Enable PT100 calibration upper limit digital
3: Enable PT1000 calibration lower limit digital
4: Enable PT1000 calibration upper limit digital
For example:
When P92.26=1, P94.09 is transferred to P92.18,
and P92.26=0.
0
○
P92.27
Anti-snag
protection braking
torque
Output
frequency
S-terminal
anti-snag
protection
command
P92.28
P92.29
Output
torque
P92.27
Anti-snag indicates that the VFD outputs reserve
torque so that the motor can stop at the fastest
speed. A smaller value of P92.28 indicates a faster
braking speed. When the motor decelerates to
P92.29, the VFD stops.
P92.27 setting range: 0.0
–300.0% (of the motor
rated current)
P92.28 setting range: 0.000
–10.000s
P92.29 setting range: 0.00
–30.00Hz
0.0%
○
P92.28
Braking torque
ACC/DEC time
0.200s
○
P92.29
Braking torque
end frequency
0.10Hz
○
P92.30
Enabling set
0
–1
0
◎