3.4. Guidelines for mounting (IP66 Units)
Before mounting the drive, ensure that the chosen
location meets the environmental condition
requirements for the drive shown in section
10.1. Environmental.
The drive must be mounted vertically,
on a suitable flat surface.
The minimum mounting clearances as shown
in the table below must be observed.
The mounting site and chosen mountings
should be sufficient to support the weight
of the drives.
Using the drive as a template, or the
dimensions shown above, mark the
locations required for drilling.
Suitable cable glands to maintain the
ingress protection of the drive are required.
Gland holes for power and motor cables
are pre-moulded into the drive enclosure,
recommended gland sizes are shown below.
Gland holes for control cables may be cut as required.
The mounting location should be free from vibration.
Do not mount the drive in any area with excessive humidity, corrosive airborne chemicals or potentially dangerous dust particles.
Avoid mounting close to high heat sources.
The drive must not be mounted in direct sunlight. If necessary, install a suitable shade cover.
The mounting location must be free from frost.
Do not restrict the flow of air through the drive heatsink. The drive generates heat which must be naturally allowed to dissipate.
Correct air clearance around the drive must be observed.
If the location is subject to wide ambient temperature and air pressure variation, install a suitable pressure compensation valve in
the drive gland plate.
NOTE
If the drive has been in storage for a period longer than 2 years, the DC link capacitors must be reformed.
Drive
Size
X Above & Below
Y Either Side
Drive
Size
Cable Gland Sizes
mm
in
mm
in
Power Cable
Motor Cable
Control Cables
1
200
7.87
10
0.39
1
M20 (PG13.5)
M20 (PG13.5)
M20 (PG13.5)
2
200
7.87
10
0.39
2
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
3
200
7.87
10
0.39
3
M25 (PG21)
M25 (PG21)
M20 (PG13.5)
4
4
NOTE
Above are guidelines only and the operating ambient temperature of the drive MUST be
maintained within the limits shown in section 10.1 Environmental at all times..
3.5. Gland Plate and Lock Off
The use of a suitable gland system is required to maintain the appropriate IP / Nema rating. The gland plate has pre moulded cable
entry holes for power and motor connections suitable for use with glands as shown in the following table. Where additional holes are
required, these can be drilled to suitable size. Please take care when drilling to avoid leaving any particles within the product.
Cable Gland recommended Hole Sizes & types:
Power & Motor Cables
Control & Signal Cables
Drive Size
Power Cable
Motor Cable
Control Cables
Power Cable
Motor Cable
Control Cables
Size 1
22mm
PG13.5
M20
22mm
PG13.5
M20
Size 2 & 3
27mm
PG21
M25
22mm
PG13.5
M20
Flexible Conduit Hole Sizes:
Drive Size
Drill Size
Trade Size
Metric
Size 1
28mm
¾ in
21
Size 2 & 3
35mm
1 in
27
Mech
anical Installation
3