Par.
Description
Minimum
Maximum
Default
Units
P-25
Analog Output Function Select
0
11
8
-
Digital Output Mode. Logic 1 = +24V DC
0: Drive Enabled (Running).
Logic 1 when the Optidrive is enabled (Running).
1: Drive Healthy.
Logic 1 When no Fault condition exists on the drive.
2: At Target Frequency (Speed).
Logic 1 when the output frequency matches the setpoint frequency.
3: Drive Tripped.
Logic 1 when the drive is in a fault condition.
4: Output Frequency >= Limit.
Logic 1 when the output frequency exceeds the adjustable limit set in P-19.
5: Output Current >= Limit.
Logic 1 when the motor current exceeds the adjustable limit set in P-19.
6: Output Frequency < Limit.
Logic 1 when the output frequency is below the adjustable limit set in P-19.
7: Output Current < Limit.
Logic 1 when the motor current is below the adjustable limit set in P-19.
Analog Output Mode
8: Output Frequency (Motor Speed).
0 to P-01, resolution 0.1Hz.
9: Output (Motor) Current.
0 to 200% of P-08, resolution 0.1A.
10: Output Power.
0 – 200% of drive rated power.
11: Load Current.
0 – 200% of P-08, resolution 0.1A.
P-30
Start Mode, Automatic Restart, Fire Mode Operation
Index 1: Start Mode & Automatic Restart
N/A
N/A
Edge-r
-
Selects whether the drive should start automatically if the enable input is present and latched during power on. Also configures the
Automatic Restart function.
: Following Power on or reset, the drive will not start if Digital Input 1 remains closed. The Input must be closed after a power on
or reset to start the drive.
: Following a Power On or Reset, the drive will automatically start if Digital Input 1 is closed.
To
: Following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The
numbers of restart attempts are counted, and if the drive fails to start on the final attempt, the drive will trip with a fault, and will require the
user to manually reset the fault. The drive must be powered down to reset the counter.
Index 2: Fire Mode Input Logic
0
1
0
-
Defines the operating logic when a setting of P-15 is used which includes Fire Mode, e.g. settings 15, 16, 17 & 18.
0: Normally Closed (NC) Input.
Fire Mode active if input is open.
1: Normally Open (NO) Input.
Fire Mode active if input is closed.
Index 3: Fire Mode Input Type
0
1
0
-
Defines the input type when a setting of P-15 is used which includes Fire Mode, e.g. settings 15, 16, 17 & 18.
0: Maintained Input.
The drive will remain in Fire Mode, only as long the fire mode input signal remains
(Normally Open or Normally Closed operation is supported depending on Index 2 setting).
1: Momentary Input.
Fire Mode is activated by a momentary signal on the input. Normally Open or Normally Closed operation is
supported depending on Index 2 setting. The drive will remain in Fire Mode until disabled or powered off.
P-31
Keypad Start Mode Select
0
7
1
-
This parameter is active only when operating in Keypad Control Mode (P-12 = 1 or 2) or Modbus Mode (P-12 = 3 or 4). When settings 0,
1, 4 or 5 are used, the Keypad Start and Stop keys are active, and control terminals 1 and 2 must be linked together. Settings 2, 3, 6 and 7
allow the drive to be started from the control terminals directly, and the keypad Start and Stop keys are ignored.
0: Minimum Speed, Keypad Start
1: Previous Speed, Keypad Start
2: Minimum Speed, Terminal Enable
3: Previous Speed, Terminal Enable
4: Current Speed, Keypad Start
5: Preset Speed 4, Keypad Start
6: Current Speed, Terminal Start
7: Preset Speed 4, Terminal Start