Version 1.00
| Optidrive ODE-3 IP66 Outdoor Rated User Guide |
27
www.invertekdrives.com
6.3.4. Common Functions
Parameter Access Control and Locking (relevant parameters)
Par.
Description
Minimum
Maximum
Default
Units
P-14
Extended Menu Access code
0
65535
0
-
Enables access to Extended and Advanced Parameter Groups. This parameter must be set to the value programmed in P-37 (default:
101) to view and adjust Extended Parameters and value of P-37 + 100 to view and adjust Advanced Parameters. The code may be
changed by the user in P-37 if desired.
P-37
Access Code Definition
0
9999
101
-
Defines the access code which must be entered in P-14 to access parameters above P-14.
P-38
Parameter Access Lock
0
1
0
-
0: Unlocked.
All parameters can be accessed and changed.
1: Locked.
Parameter values can be displayed, but cannot be changed except P-38.
Local/Remote (relevant parameters)
Par.
Description
Minimum
Maximum
Default
Units
P-15
Digital Input Function Select
0
17
0
-
Defines the function of the digital inputs depending on the control mode setting in P-12. See section 7. Analog and Digital Input Macro
Configurations for more information.
Preset Speeds (relevant parameters)
Par.
Description
Minimum
Maximum
Default
Units
P-15
Digital Input Function Select
0
17
0
-
Defines the function of the digital inputs depending on the control mode setting in P-12. See section 7. Analog and Digital Input Macro
Configurations for more information.
P-20
Preset Frequency / Speed 1
-P-01
P-01
5.0
Hz / RPM
P-21
Preset Frequency / Speed 2
-P-01
P-01
25.0
Hz / RPM
P-22
Preset Frequency / Speed 3
-P-01
P-01
40.0
Hz / RPM
P-23
Preset Frequency / Speed 4
-P-01
P-01
P-09
Hz / RPM
Preset Speeds / Frequencies selected by digital inputs depending on the setting of P-15.
If P-10 = 0, the values are entered as Hz. If P-10 > 0, the values are entered as RPM.
NOTE
Changing the value of P-09 will reset all values to factory default settings.
Start Mode, Auto Restart and Fire Mode (relevant parameters)
Par.
Description
Minimum
Maximum
Default
Units
P-15
Digital Input Function Select
0
17
0
-
Defines the function of the digital inputs depending on the control mode setting in P-12. See section 7. Analog and Digital Input Macro
Configurations for more information.
Parameters