   |   Optidrive ODE-3 IP66 Outdoor Rated User Guide   |   

Version 1.00

www.invertekdrives.com

Serial Communication Configuration

Par.

Description

Minimum

Maximum

Default

Units

P-36

Serial Communications Configuration

See Below

Index 1 : Drive Address

1

63

1

-

Index 2 : Baud Rate & Network Type

9.6

1000

115.2

kbps

Index 3 : Modbus RTU / Optibus Communication loss 

timeout protection

0

60000

300

ms

This parameter has three sub settings used to configure the Modbus RTU Serial Communications. The Sub Parameters are:

Index 1 : Drive Address :

 Range : 0 – 63, default : 1

Index 2: Baud Rate & Network type:

 Selects the baud rate and network type for the internal RS485 communication port.

For Modbus RTU: Baud rates 9.6, 19.2, 38.4, 57.6, 115.2 kbps are available.
For CAN: Baud rates 125, 250, 500 & 1000 kbps are available.

Index 3: Modbus RTU / Optibus Communication loss timeout protection:

 Defines the time for which the drive will 

operate without receiving a valid command telegram after the drive has been enabled. This applies to Modbus RTU networks and 

Optibus networks (e.g. keypad control or Master Slave operation) only. CAN communication loss function is enabled via CAN 

objects 100Ch and 100Dh. Setting 0 disables the Watchdog timer. Setting a value of 30, 100, 1000, or 3000 defines the time limit 

in milliseconds for operation. A ‘

’ suffix selects trip on loss of communication. An ‘



’ suffix means that the drive will coast stop (output 

immediately disabled) but will not trip.

Current Limit (relevant parameters)

Par.

Description

Minimum

Maximum

Default

Units

P-54

Maximum Current Limit

0.0

175.0

150.0

%

Defines the max current limit in vector control modes

6.3.4. Advanced Functions
Autotune (relevant parameters)

Par.

Description

Minimum

Maximum

Default

Units

P-52

Motor Parameter Autotune

0

1

0

-

0: Disabled
1: Enabled.

 When enabled, the drive immediately measures required data from the motor for optimal operation. Ensure all motor 

related parameters are correctly set first before enabling this parameter.
This parameter can be used to optimise the performance when P-51 = 0.
Autotune is not required if P-51 = 1.
For settings 2 – 5 of P-51, autotune MUST be carried out AFTER all other required motor settings are entered.

Motor Control Methods

Optidrive E3 may be used with the following motor types:

  

Asynchronous Induction Motors (IM)

  

Synchronous Permanent Magnet AC Motors (PM)

  

Brushless DC Motors (BLDC)

  

Synchronous Reluctance Motors (SynRM)

  

Line Start Permanent Magnet Motors (LSPM)

Each motor type requires the correct operating mode to be selected and the correct commissioning procedure to be followed as 
described in the following sections.

Parameters

Par.

Description

Minimum

Maximum

Default

Units

P-07

Motor Rated Voltage/ Back EMF at rated speed (PM/ BLDC)

0

250 / 500

230 / 400

V

For Induction Motors, this parameter should be set to the rated (nameplate) voltage of the motor (Volts).
For Permanent Magnet or Brushless DC Motors, it should be set to the Back EMF at rated speed.

Parameters

6

Summary of Contents for OPTIDRIVE E3

Page 1: ...Input User Manual 1 Quick Start Up 2 General Information and Ratings 3 Mechanical Installation 4 Power Control Wiring 5 Operation 6 Parameters 7 Analog and Digital Input Macro Configurations 8 Modbus...

Page 2: ...Resetting a Fault 18 5 7 LED Display 19 6 Parameters 20 6 1 Standard Parameters 20 6 2 Parameter List 20 6 3 Parameter Functions 22 6 4 P 00 Read Only Status Parameters 36 7 Analog and Digital Input M...

Page 3: ...very installation or commissioning The manufacturer also accepts no liability for damage or consequences resulting from inappropriate negligent or incorrect installation incorrect adjustment of the op...

Page 4: ...e according to any local legislation or codes Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Danger Indicates a potentia...

Page 5: ...f Input Phases 2 200 240 4 380 480 Output Current x 10 2 2 Product Rating Label Location All Optidrive E3 models carry a rating label which can be located as follows On right hand side when viewed fro...

Page 6: ...120043 3F1 ODE 3 120043 301 0 75 1 4 3 1 ODE 3 120070 3F1 ODE 3 120070 301 1 5 2 7 1 ODE 3 220070 3F4 ODE 3 220070 304 1 5 2 7 2 ODE 3 220105 3F4 ODE 3 220105 304 2 2 3 10 5 2 ODE 3 320180 3F4 ODE 3 3...

Page 7: ...tal 3 2 UL Compliant Installation Refer to section 10 4 Additional Information for UL Compliance on page 48 for Additional Information for UL Compliance 3 3 Mechanical Dimensions IP66 Nema 4X Enclosed...

Page 8: ...orrect air clearance around the drive must be observed If the location is subject to wide ambient temperature and air pressure variation install a suitable pressure compensation valve in the drive gla...

Page 9: ...al Cover To access the connection terminals the drive front cover needs to be removed as shown IP66 Nema 4X Units Removing the screws on the front of the product allows access to the connection termin...

Page 10: ...Frame sizes 2 3 and 4 Single phase supply 3 phase supply L1 L3 EMC L2 N U V W 1 2 3 4 5 6 7 8 9 10 11 I0I0I I0I0I BR A B C D L1 L3 EMC L2 N U V W 1 2 3 4 5 6 7 8 9 10 11 I0I0I I0I0I A C BR D B A Inco...

Page 11: ...Incoming Power Connection 4 4 12 C Fuse Circuit Breaker Selection 4 4 2 12 D Optional Input Choke 4 4 3 13 E Optional External EMC Filter 4 10 17 F Internal Disconnect Isolator 4 3 14 G Optional Brake...

Page 12: ...e used The device must be suitable for protecting equipment with a DC component in the leakage current Individual ELCBs should be used for each Optidrive Shield Termination Cable Screen The safety gro...

Page 13: ...e U V and W terminals using a suitable 3 or 4 core cable Where a 3 core cable is utilised with the shield operating as an earth conductor the shield must have a cross sectional area at least equal to...

Page 14: ...ssage 4 Use UP or DOWN key to select the option Lc OFF means integrated switches are enabled Lc On means the switches are locked disabled 5 Press the STOP button again to exit Switch Position Paramete...

Page 15: ...Volt Common internally connected to terminal 7 10 Relay Common 1 1 Relay NO Contact Contact 250Vac 6A 30Vdc 5A intended for resistive load 4 10 1 Analog Output The analog output function may be confi...

Page 16: ...ble for fixed installation with relevant mains voltage with a concentric protection wire Installation of a standard cable within a suitable steel or copper tube is also acceptable 3 A cable suitable f...

Page 17: ...START When in keypad mode used to Start a stopped drive or to reverse the direction of rotation if bi directional keypad mode is enabled 5 2 Operating Displays Drive Stopped Disabled Drive is enabled...

Page 18: ...ys to select the required Read Only parameter Press the Navigate key for 1 second to display the value Press and hold the Navigate key 2 seconds to return to the operating display 5 5 Resetting Parame...

Page 19: ...rder to display certain warnings the following methods are used 5 7 1 LED Display Layout 8 8 8 8 8 8 a b c d e f 5 7 2 LED Display Meanings LED Segments Behaviour Meaning a b c d e f Flashing all toge...

Page 20: ...that the drive is enabled and the user tries to change the parameter an L is shown on the left of the display 6 2 Parameter List 6 2 1 Standard Parameters Par Function Page No P 01 Maximum Frequency S...

Page 21: ...Parameter Access Lock 26 P 39 Analog Input 1 Offset 25 P 40 Index 1 Display Scaling Factor 29 Index 2 Display Scaling Source 29 P 41 PI Controller Proportional Gain 30 P 42 PI Controller Integral Tim...

Page 22: ...d Maximum Speed Preset Speeds etc will also be displayed in RPM NOTE If P 09 value is changed P 10 value is reset to 0 Optidrive E3 normally uses frequency for all speed related parameters e g Minimum...

Page 23: ...ed Limits relevant parameters These parameters define the range of output frequency and therefore the speed range through which the drive will operate As described above If P 10 0 Values are Hz If P 1...

Page 24: ...by reducing motor flux This function should not be used in applications which have large sudden load step changes or for PI control applications as it may cause instability in the control or over cur...

Page 25: ...ence after scaling and offset are applied is 0 0 100 signal means the output frequency speed will be the value set in P 01 Uni polar 0 to 10 Volt Signal bi directional operation The drive will operate...

Page 26: ...urrent Limit Logic 1 when the motor current exceeds the adjustable limit set in P 19 6 Output Frequency Limit Logic 1 when the output frequency is below the adjustable limit set in P 19 7 Output Curre...

Page 27: ...ng on the control mode setting in P 12 See section 7 Analog and Digital Input Macro Configurations for more information Preset Speeds relevant parameters Par Description Minimum Maximum Default Units...

Page 28: ...is closed To Following a trip the drive will make up to 5 attempts to restart at 20 second intervals The numbers of restart attempts are counted and if the drive fails to start on the final attempt th...

Page 29: ...on relevant parameters Par Description Minimum Maximum Default Units P 17 Maximum Effective Switching Frequency 4 32 8 kHz Sets maximum effective switching frequency of the drive If rEd is displayed w...

Page 30: ...pper enabled with software protection for a 200W continuous rated resistor 2 Enabled Without Software Protection Enables the internal brake chopper without software protection An external thermal prot...

Page 31: ...0 0 100 0 0 0 When P 44 0 this parameter sets the preset digital reference setpoint used for the PI Controller as a of the feedback signal P 46 PI Feedback Source Select 0 5 0 Selects the source of t...

Page 32: ...drive will coast stop output immediately disabled but will not trip Current Limit relevant parameters Par Description Minimum Maximum Default Units P 54 Maximum Current Limit 0 0 175 0 150 0 Defines t...

Page 33: ...hms Determined by Autotune adjustment is not normally required P 56 Motor Stator d axis Inductance Lsd 0 00 655 35 mH Determined by Autotune adjustment is not normally required P 57 Motor Stator q axi...

Page 34: ...MF exceeds 800V the drive may be permanently damaged Commissioning Procedure When operating with permanent magnet motors the commissioning steps are as follows Enter the motor Back EMF at Rated Freque...

Page 35: ...lowing the setting of this parameter o The drive output will be enabled and the motor shaft may move It is important to ensure this is safe before carrying out the autotune o For SynRM motors the auto...

Page 36: ...time with heatsink 85 C Hours Total accumulated hours and minutes of operation above heatsink temp of 85 C P00 24 Accumulated time with drive internal temp 80 C Hours Total accumulated hours and minut...

Page 37: ...is present P 31 When Keypad Mode is selected determines at what output frequency speed the drive should start following the enable command and also whether the keypad start key must be pressed or if t...

Page 38: ...Open Rising Edge Close momentarily to START the drive in the forward direction NC STOP Input must be maintained START REV Normally Open Rising Edge Close momentarily to START the drive in the reverse...

Page 39: ...Analog Input AI1 3 7 STOP RUN FWD STOP RUN REV E TRIP OK Analog Input AI1 3 FAST STOP P 24 8 STOP RUN FWD REV DI3 DI4 PR 2 0 0 P 20 1 0 P 21 0 1 P 22 1 1 P 23 9 STOP START FWD STOP START REV DI3 DI4 P...

Page 40: ...18 STOP RUN AI1 REF KPD REF Fire Mode AI1 1 9 10 11 12 13 Behavior as per setting 0 7 6 Macro Functions Fieldbus Control Mode P 12 3 4 7 8 or 9 P 15 DI1 DI2 DI3 AI2 DI4 AI1 Diagram 0 1 0 1 0 1 0 1 0...

Page 41: ...e drive in emergency conditions until the drive is no longer capable of sustaining operation The Fire Mode input may be a normally open Close to Activate Fire Mode or Normally Closed Open to Activate...

Page 42: ...un Enable Bit 1 Low Decel Ramp 1 P 04 High Decel Ramp 2 P 24 Bit 2 Low No Function High Fault Reset Bit 3 Low No Function High Coast Stop Request 2 R W Modbus Speed reference setpoint 0 5000 Setpoint...

Page 43: ...eters may not be changed whilst the drive is enabled for example Optidrive E3 provides the following default COB ID and functions Type COB ID Function NMT 000h Network management Sync 080h Synchronous...

Page 44: ...onous The received data will be transferred to the drive active control register when the next sync message is received 254 255 Asynchronous The received data will be transferred to the drive active c...

Page 45: ...d object RW U32 N 20010010h 3 RX PDO1 3rd mapped object RW U32 N 20030010h 4 RX PDO1 4th mapped object RW U32 N 00060010h 1601h 0 RX PDO2 1 mapping no of entries RW U8 N 4 1 RX PDO2 1st mapped object...

Page 46: ...start stop function is controlled by drive control terminals Reset function bit 2 works all the time as long as drive is operated under Modbus control mode P 12 3 or 4 9 2 2 Speed Reference Format Spe...

Page 47: ...3 1 1 5 2 9 5 16 15 8 8 7 2 1 5 2 8 9 16 15 8 8 7 100 2 2 2 3 12 1 16 17 5 8 8 10 5 50 3 4 5 20 9 32 30 8 8 18 25 3 5 5 7 5 26 4 40 35 8 8 24 20 4 7 5 10 33 3 40 45 16 5 30 15 4 1 1 15 50 1 63 70 16 5...

Page 48: ...her applicable local codes Motor Cable 75 C Copper must be used Power cable connections and tightening torques are shown in section 3 3 Mechanical Dimensions IP66 Nema 4X Enclosed Units Integral Solid...

Page 49: ...connected check if the motor is too hot 12 Optibus comms loss Check communication link between drive and external devices Make sure each drive in the network has its unique address 13 DC bus ripple t...

Page 50: ...rol word from 0 to 1 In the event of O I hO I or I t trp faults in order to prevent damage that may occur through repeatedly enabling the drive into a fault condition these trips cannot be reset immed...

Page 51: ...Version 1 00 Optidrive ODE 3 IP66 Outdoor Rated User Guide 51 www invertekdrives com...

Page 52: ...Invertek Drives Ltd Offa s Dyke Business Park Welshpool Powys SY21 8JF United Kingdom Tel 44 0 1938 556868 Fax 44 0 1938 556869 www invertekdrives com...

Reviews: