Version 1.00
| Optidrive ODE-3 IP66 Outdoor Rated User Guide |
41
www.invertekdrives.com
7.7. Macro Functions - User PI Control Mode (P-12 = 5 or 6)
P-15
DI1
DI2
DI3 / AI2
DI4 / AI1
Diagram
0
1
0
1
0
1
0
1
0
STOP
ENABLE
PI REF
P-20 REF
AI2
AI1
4
1
STOP
ENABLE
PI REF
AI1 REF
AI2 (PI FB)
AI1
4
3, 7
STOP
ENABLE
PI REF
P-20
E-TRIP
OK
AI1 (PI FB)
3
4
(NO)
START
(NC)
STOP
AI2 (PI FB)
AI1
12
5
(NO)
START
(NC)
STOP
PI REF
P-20 REF
AI1 (PI FB)
5
6
(NO)
START
(NC)
STOP
E-TRIP
OK
AI1 (PI FB)
8
STOP
RUN
FWD
REV
AI2 (PI FB)
AI1
4
14
STOP
RUN
-
-
E-TRIP
OK
AI1 (PI FB)
16
15
STOP
RUN
P-23 REF
PI REF
Fire Mode
AI1 (PI FB)
1
16
STOP
RUN
P-23 REF
P-21 REF
Fire Mode
AI1 (PI FB)
1
17
STOP
RUN
P-21 REF
P-23 REF
Fire Mode
AI1 (PI FB)
1
18
STOP
RUN
AI1 REF
PI REF
Fire Mode
AI1 (PI FB)
1
2, 9, 10, 11, 12, 13 = Behavior as per setting 0
NOTE
P1 Setpoint source is selected by P-44 (default is fixed value in P-45, AI 1 may also be selected).
P1 Feedback source is selected by P-46 (default is AI 2, other options may be selected).
7.8. Fire Mode
The Fire Mode function is designed to ensure continuous operation of the drive in emergency conditions until the drive is no longer
capable of sustaining operation. The Fire Mode input may be a normally open (Close to Activate Fire Mode) or Normally Closed
(Open to Activate Fire Mode) according to the setting of P-30 Index 2. In addition, the input may be momentary or maintained type,
selected by P-30 Index 3.
This input may be linked to a fire control system to allow maintained operation in emergency conditions, e.g. to clear smoke or
maintain air quality within that building.
The fire mode function is enabled when P-15 = 15, 16, 17 or 18, with Digital Input 3 assigned to activate fire mode.
Fire Mode disables the following protection features in the drive:
O-t (Heat-sink Over-Temperature), U-t (Drive Under Temperature), Th-FLt (Faulty Thermistor on Heat-sink), E-trip (External Trip),
4-20 F (4-20mA fault), Ph-Ib (Phase Imbalance), P-Loss (Input Phase Loss Trip), SC-trp (Communications Loss Trip), I.t-trp (Accumulated
overload Trip).
The following faults will result in a drive trip, auto reset and restart:
O-Volt (Over Voltage on DC Bus), U-Volt (Under Voltage on DC Bus), h O-I (Fast Over-current Trip), O-I (Instantaneous over current
on drive output), Out-F (Drive output fault, Output stage trip).
Analog and Digital Input Macr
o Configurations
7