4.9. Using the Internal Pot (Switched Versions)
On switched drives, the built in pot (indicated) may be used to directly control the signal level applied to analog input 1, and therefore
the output frequency (motor speed).
To select the built in pot as the signal source for analog input 1,
set P-17 = In-pot.
4.10. Control Terminal Connections
Default Connections
Control Terminal
Signal
Description
1
+24Vdc User Output
+24Vdc user output, 100mA.
Do not connect an external voltage source to
this terminal.
2
Digital Input 1
Positive logic
“Logic 1” input voltage range: 8V … 30V DC
“Logic 0” input voltage range: 0V … 4V DC
3
Digital Input 2
4
Digital Input 3 /Analog
Input 2
Digital: 8 to 30V
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
5
+10V User Output
+10V, 10mA, 1kΩ minimum
6
Analog Input 1 /
Digital Input 4
Analog: 0 to 10V, 0 to 20mA or 4 to 20mA
Digital: 8 to 30V
7
0V
0 Volt Common, internally connected to terminal 9
8
Analog Output /
Digital Output
Analog: 0 to 10V,
Digital: 0 to 24V
20mA maximum
9
0V
0 Volt Common, internally connected to terminal 7
10
Relay Common
11
Relay NO Contact
Contact 250Vac, 6A / 30Vdc, 5A intended for resistive
load
4.10.1. Analog Output
The analog output function may be configured using parameter P-25, which is described in section 6.2. Parameter List on page 20.
The output has two operating modes, dependent on the parameter selection:
Analog Mode
o The output is a 0 – 10 volt DC signal, 20mA max load current.
Digital Mode
o The output is 24 volt DC, 20mA max load current.
4.10.2. Relay Output
The relay output function may be configured using parameter P-18, which is described in section 6.2. Parameter List on page 20.
4.10.3. Analog Inputs
Two analog inputs are available, which may also be used as Digital Inputs if required. The signal formats are selected by parameters
as follows:
Analog Input 1 Format Selection Parameter P-16.
Analog Input 2 Format Selection Parameter P-47.
These parameters are described more fully in section 6.2. Parameter List on page 20.
The function of the analog input, e.g. for speed reference or PID feedback for example is defined by parameters P-15. The function of
these parameters and available options is described in section 7. Analog and Digital Input Macro Configurations on page 37.
Power & Contr
ol Wiring
4