CONCEPT IQ. PLUS Programmer’s Manual.
Operation.
a) When an Autoarm Area is disarmed, the Re-Autoarm timer will be started for that Area.
b) While the timer is running, any Zone Input activity detected in the Area will cause the timer to be re-started. (Thereby preventing the
Area from Re-arming)
c) When the Re-Autoarm timer has run for the specified time without detecting any Zone Input activity, the Area will automatically be Re-
armed.
To implement the Re-Autoarm feature, the following options must be programmed:
1) The Area must be programmed as an Autoarm Area. i.e. A TimeZone must be assigned to the Area in the Area Arming options.
( Address 551 [Area 1] to 554 [Area 4] )
NOTE: If you do not wish the Area to turn On at the End time specified in the TimeZone, assign a TimeZone that has the Start and End
times programmed to 00:00.
2) Program a “Re-Autoarm Time” to a value of 1 to 255 Minutes to specify how long the Area can remain dis-armed without detecting any
Zone Input activity. (If this period expires without any Zone Input activity being detected, the Area will automatically arm)
3) It is recommended that the Auto-Arm Pre-Warn Time (Address 907) and/or Area Exit Delay Time (Address 541 to 544) is programmed
for the Area/s to provide a warning that the Area is about to automatically Arm.
Settings:
0
There will be no Re-autoarm function.
1 to 255
Re-Autoarm Timer Value.
ENHANCED TERMINAL AUXILIARY TIME
(0 TO 255 SECONDS) (RF AND ACCESS)
Sets the time period that the Auxiliaries on an RF Terminal will be activated when a Wireless Remote Key activates an Auxiliary Event.
SIREN HOLD-OFF TIME (0 TO 255 SECONDS)
Sets the time period that the activation of the Siren Speaker output will be delayed after an alarm event occurs.
Applies to Siren Speaker O/P & Auxiliary Event Type 9.
“24 HR FIRE” ZONE (SMOKE DETECTOR) IGNORE TIME
(0 TO 255 SECONDS)
This timer is activated on any “Smoke Detector Reset” Auxiliary Event and sets the time period that the system will ignore alarms on Zones
programmed as Zone Type 11 - “24 Hour Fire”.
WALK TEST TIME
(0 TO 255 MINUTES)
This timer is activated when a Walk Test is started and sets the time that the system will remain in Walk Test mode before automatically
ADDRESS
DEFAULT
FUNCTION
(Data Type)
909
910
911
912
5 Seconds
0 Seconds
60 Seconds
30 Minutes