p70
Ver. 3.003 (24/4/03)
CONCEPT IQ. PLUS Programmer’s Manual.
905
906
907
908
5 Minutes
0 Minutes
255 Seconds
30 Minutes
-
The Zone Input must have at least one Area assigned.
The Siren Time does not apply to System Inputs. Siren operation for System Inputs is determined by the settings in Address 897 - System
Input Siren enable, and Address 890, Option 7 - Enable Special Siren Tone for System Alarms.
KEYPAD LOCKOUT TIME (0 TO 255 MINUTES)
Sets the period of time that the keypad will be locked out after 5 incorrect PIN Code login attempts in a row.
For Keypad Lockout to function, the setting must be non-zero.
Siren activation for Keypad Lockout can be enabled in Address 897, Option 4.
Dialer activation for Keypad Lockout can be enabled in Address 898, Option 4.
AC REPORT DELAY(0 TO 255 MINUTES)
Sets the period of time that the 16V AC input must be continuously disconnected before an AC Fail Alarm is reported.
CAUTION:
If an AC Report Delay time is programmed, the system Owner/User must be made aware that if the AC supply fails and the
Battery is in poor condition, the system may shut down before the AC faill is reported to the Central Monitoring Station, leaving the premises
unmonitored and/or unprotected.
If an AC Report Delay is required, ensure that Automatic Battery testing is enabled (Address 892, Option 2), keep the delay period as short
as possible and advise the system Owner/User of the implications of the function.
AUTO-ARM PRE-WARN TIME (WARNING TIME BEFORE AN AUTO-ARM OCCURS)
(0 TO 255 SECONDS)
Sets the period of time that a warning indication will be provided when an Area is about to be automatically armed by a TimeZone, or by
the Re-Autoarm function.
A value of 0 means no Pre-warning. Note that the Pre-warn time is added to the Auto-arm time. e.g. If the Area is programmed to arm at 7
PM with a Pre-warn time of 120 Seconds, the Area will arm at 7:02 PM.
The Autoarm Pre-warn indication is provided by Terminals associated with the Area about to be armed, and by the relevant Auxiliary Event
Types; 46 (Area 1) to 49 (Area 4).
RE-AUTO-ARM TIME (PERIOD OF NO ZONE ACTIVITY BEFORE AREA WILL AUTO-ARM)
(0 TO 255 MINUTES)
The Re-Autoarm function allows one or more Areas to be programmed to automatically arm when no activity is detected on the Zone Inputs
in the Area for a specified period of time. This function can be used for a number of purposes including:
•
The ability to ensure that Areas are not accidently left dis-armed when all personnel have vacated the site.
•
Turning off particular building services (lights, aircon, etc) when no personnel are detected in the Area.
•
Keyswitch or Button operated “Deadman” functions.