p62
Ver. 3.003 (24/4/03)
CONCEPT IQ. PLUS Programmer’s Manual.
TIMEZONE DAYS OF THE WEEK
1
Sunday
5
Thursday
2
Monday
6
Friday
3
Tuesday
7
Saturday
4
Wednesday
8
Holiday
Options 1 to 7:
The TimeZone will be valid on the specified Day, or Days, unless the date has been defined as a Holiday.
Option 8:
The TimeZone will always be valid on the Days of the Week selected, regardless of whether the date has been
defined as a Holiday.
AUXILIARY PROGRAMMING OVERVIEW
Auxiliary Programming sets the programming options for the ten Auxiliaries AUXILIARY 1 to AUXILIARY 10.
Each Auxiliary has 3 Addresses related to the programming.
•
The Auxiliary Event Type must be programmed to detemine which Entity or Event will the control the Auxiliary.
•
The Auxiliary Timer Value determines the period of time the Auxiliary will be activated if a Timed Auxiliary Action is selected.
•
The Auxiliary Action must be programmed to define the way in which the Auxiliary is controlled.
AUXILIARY EVENT TYPE
The Auxiliary Event Type detemines which Entity or Event will the control the Auxiliary.
To define the way in which the Auxiliary is controlled, the “Auxiliary Action” must also be programmed.
Programming Addresses for Auxiliary Event Type programming:
A single Auxiliary Event Type can be assigned to each of the general purpose Auxiliary outputs. (Auxiliaries 1 to 10)
If the General Option “Siren O/P operates as Auxiliary” is selected, (Address 892, Option 6) an Auxiliary Event Type can also be assigned to
Auxiliary 0, the Siren Speaker output.
(Option Data)
Spare
(Value Data)
Aux 1
Type 1 - Burglary
Aux 2
Type 10 - Int Siren
770-799
800-810
ADDRESS
DEFAULT
FUNCTION
(Data Type)
Auxiliary
0
1
2
3
4
5
6
7
8
9
10
Address
800
801
802
803
804
805
806
807
808
809
810