WIRELESS REMOTE CONTROL
1) Ensure that an RF Terminal or RF Module is connected to the LAN and commissioned as described in the installation instructions of these products.
2) If a “Bell Squawk” on the Siren (or another Auxiliary Output), and/or Flashing on the Strobe is required to indicate successful Wireless operations:
Enable Option 3 - “Bell Squawk on Siren for Wireless operations” in General Options 2.
NEXT 891
Enable Option 7 - “
Flash on Strobe for Wireless Remote Key operations
” in General Options 3.
NEXT 892
3) If an Auxiliary Output is required to provide the “Bell Squawk” indications.
a) Choose the Auxiliary to control and select Event Type 16 - “Bell Squawk”.
NEXT 801 (Aux 1), to 810 (Aux 10)
b) Check that the “Auxiliary Action” for the selected Auxiliary is set to Type 0 - “Follow Event Status”.
NEXT 861 (Aux 1), to 870 (Aux 10)
4) If an Auxiliary Output is required to be controlled by Button 4 on the Wireless Remote Key:
a) Choose the Auxiliary to control and select Event Type 17 - “RF Auxiliary”.
NEXT 801 (Aux 1), to 810 (Aux 10)
b) Program an Auxiliary Timer value for the selected Auxiliary.
NEXT 831 (Aux 1), to 840 (Aux 10)
c) Assign the required “Auxiliary Action” for the selected Auxiliary.
NEXT 861 (Aux 1), to 870 (Aux 10)
2 - One-shot timed in Seconds.
3 - One-shot timed in Minutes.
Types 4 to 13 may also be suitable.
WALK TESTING
1) Program the “Walk Test Time” (0 to 255 Minutes. Factory Default = 30 Minutes)
NEXT 912
(Maximum period that the system can remain in Walk Test Mode)
2) Program/Check the Users who require access to Walk Test Mode.
NEXT 403 to 447
Program a PIN Code, Assign the Area/s required, and set the User Type to Type 7 - “Master”.
ZONE SELF TESTING
1) Enable Self Test operation for any Zone Inputs that are to be automatically tested by the system.
Enable Option 5 - “Self Test Zone” in the Zone Options.
NEXT 651 (Zone 1) to 666 (Zone 16)
2) Program the Zone Self Test Period. (0 to 15. Factory Default = 0)
NEXT 903
0 = Zone Self Test Disabled.
1 to 15 = Number of Arming periods to be included in Zone Self Test processing.
3) Enable Zone Self Test Fail Reporting via Dialler if required.
NEXT 898
Enable Option 8 - “Zone Self-Test Fail”.