Programming Manual
68
Maintenance operations
27.6 Testing the local network
FROM COMPUTER
Not available.
On first power-up, or during maintenance, it may become necessary to check the presence of control
panels in the network.
FROM PANEL
<any key>,
7 Maintenance, <code>, 6 TEST Network,
or
<any key>,
7 <code> 6
Press and to view the control panels
in the network.
Press on the control panel you wish to
ping. After a moment, if the ping is
successful, the following message will
appear:
If the message “NO ANSWER !” appears,
refer to the Installation Manual Chapter
9 - Troubleshooting.
27.7 Loop Diagnostics
FROM COMPUTER
Not available.
This menu will allow you to carry out diagnostics on all the devices connected to the loop. At the end
of the diagnostics phase, the control panel will show: the maximum level of contamination, the
detector concerned, the average level of contamination, the value read on all the devices and (in
relation to the supported protocol) the quality of the reception signal of each loop device.
FROM PANEL
<any key>,
7 Maintenance, <code>, 7 Loop Diagnostics,
or
<any key>,
7 <code> 7
Press keys and to navigate through
the loops.
Press key on the loop you wish to
check.
Press keys and to move through the
parameters.
0 0 1 T h i s P a n e l
0 0 2 C o n t r o l p a n e l 0 2
0 0 3 C o n t r o l p a n e l 0 3
0 0 4 N O T i n C o n f i g u r a t i o n
C o n t r o l p a n e l 0 1 P R E S E N T
R e s p o n s e t i m e : 0 0 1 2 . 4 5 m s
1 L o o p 1 < L o o p D e s c r i p t i o n >
2 L o o p 2 < L o o p D e s c r i p t i o n >
3 L o o p 3 N o t a v a i l a b l e
4 L o o p 4 N o t a v a i l a b l e
< L o o p D e s c r i p t i o n >
D e t e c t o r s : y y y
I N M o d u l e : y y y
O U T M o d u l e : y y y