39
Table 4.2 Possible installation preparation tasks
Application
Service task
Conversion from fixed DC power source to any other
operational power source
Acquire the Conduit-hub Plug Kit and complete installation.
Do not
reinstall any used conduit-hub plug components; once removed a
plug's seal is compromised and other plug components may become
altered or damaged.
Communication
Ethernet
Conduit-hub plug removal
Conversion from Ethernet to non-Ethernet
Acquire the Conduit-hub Plug Kit and complete installation.
Do not
reinstall any used conduit-hub plug components; once removed a
plug's seal is compromised and other plug components may become
altered or damaged.
Installation
The RGX Gateway is suitable for use in Class I, Division 2, Groups A, B, C and D classified areas OR non-
hazardous locations only.
x
Class I, Division 2, Groups A B C D; Temp Code T6
x
Ambient Temperature
Ǧ
20°C to +55°C
WARNING:
Only
one of the following power input ports is permitted to be connected at a given time: 12V
Charger Port, IS Power Port, or 9–30 VDC Terminal Block.
Based on the operational power the unit will use and whether or not an Ethernet connection will be
installed, complete
only one
of two possible instruction sets as indicated below in Table 4.3.
Read the full
instruction set before starting.
Along with the information supplied in the instruction set, meet the
requirements of the AHJ, and consult the control drawing 1810D9509-200 located in this "Product Manual,
Appendix A Supplemental information about external power connections.
Table 4.3 RGX Configuration Interface instruction sets
Instruction set
Figure 4.2
Figure 4.3
Power-Ethernet combination
Excludes
fixed DC power
and
excludes
Ethernet
Yes
No
Includes
an external power source,
Ethernet, or both
No
Yes
Document Number: 0000037533
DO NOT CHANGE WITHOUT THE FOLLOWING AGENCY APPROVALS(S):N/A
Modified: 2018-05-25 13:18:14 EDT
State:In Work
INDUSTRIAL SCIENTIFIC CORPORATION
Title: PRODUCT MANUAL RGX GATEWAY-EN-1
Eng:
Drawing No: 17158071-1
Drawn By: Gaygan, Nancy
Created: 2018-05-16 10:24:51 EDT
Rev: 1
Printed By: Kuzmich, Bob
Int: 1.5
Date:May 29, 2018