INSULATING THE REFRIGERANT PIPE
You must check if there is a gas leak before completing the installation process.
Use EPDM insulation that meets the following conditions.
ITEM
UNIT
STANDARD
REMARKS
Density
g/cm²
0.048~0.096
KSM 3014-01
Dimension change route by
heat
%
-5 or less
Water absorption rate
g/cm²
0.005 or less
Thermal conductivity
kcal/m·h
·˚C
0.032 or less
KSL 9016-95
Moisture transpiration
factor
ng/(m²·s·Pa)
15 or less
KSM 3808-03
Moisture transpiration
grade
{g/(m²·24h)}
15 or less
KSA 1013-01
Formaldehyde dispersion
mg/L
-
KSF 3200-02
Oxygen rate
%
25 or less
ISO 4589-2-96
Be sure to insulate the refrigerant pipe, joints, and connections with class 'o' material.
If you insulate the pipes, the condensed water does not fall from the pipes and the capacity of the Air to Water
Heat Pump is improved.
Check if there are any insulation cracks on the bent pipe.
BRAZING THE PIPE
Make sure that there is no moisture inside the pipe.
Make sure that there are no foreign materials or impurities in the pipe.
REPLACEMENT OF NITROGEN GAS
1.
Use oxygen-free nitrogen gas when brazing the pipes as shown in the picture.
2.
If you do not use Nitrogen gas when brazing the pipes, oxidation may form in the pipe. It can cause
damage to the compressor and valves.
3.
Adjust the flow rate of the replacement with a pressure regulator to maintain 0.05 m
3
/h or more.
4. Perform brazing of the service valve after protecting the valve.
Summary of Contents for Inuit 6I
Page 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Page 16: ...16 IGLU Inuit 6WTI indoor unit...
Page 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Page 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Page 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Page 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Page 43: ...43...