60
SELECTING AN ADDITIONAL REFRIGERANT CHARGE
The basic amount of refrigerant for outdoor units charged in the factory is:
OUTDOOR UNIT (SERIES)
FACTORY CHARGE (kg)
IGLU® Inuit 6I/ IGLU® Inuit 6WTI
1.2
IGLU® Inuit 9I/ IGLU® Inuit 9WTI
1.4
IGLU® Inuit 12I/ IGLU® Inuit 12WTI
2.98
IGLU® Inuit 16I/ IGLU® Inuit 16WTI
2.98
Charge additional refrigerant according to the total length of the pipe.
Each factory charging values are determined according to a basic pipe length of 15 m.
When extra pipe lengths are required, additional charging works must be implemented as described below.
REFRIGERANT CHARGING
Additional charging amount is determined based on liquid pipe specifications.
IGLU® Inuit 6I/
IGLU® Inuit 6WTI
IGLU® Inuit 9I/
IGLU® Inuit 9WTI
IGLU® Inuit 12I/
IGLU® Inuit 12WTI
IGLU® Inuit 16I/
IGLU® Inuit 16WTI
Outdoor unit of
liquid
ø6.35
ø6.35
ø 9.52
ø 9.52
Additional charging
(g)
20 g/m
20 g/m
50 g/m
50 g/m
Additional Charge(g) = (L1-15)*20 (IGLU® Inuit 6I/ IGLU® Inuit 6WTI, IGLU® Inuit 9I/ IGLU® Inuit 9WTI)
Additional Charge(g) = (L1-15)*50 (IGLU® Inuit 12I/ IGLU® Inuit 12WTI, IGLU® Inuit 16I/ IGLU® Inuit 16WTI)
*L1-TOTAL LENGTH OF LIQUID PIPE
EXAMPLES:
IGLU® Inuit 6I, the total length of the liquid pipe is 20m.
ø6.35=(20m-15m) x20g/m=100 g.
IGLU® Inuit 12I, the total length of the liquid pipe is 20m.
ø 9.52=(20m-15m) x50g/m=250 g.
The R-410A refrigerant is blended. Add only liquid refrigerant.
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add the quantity of the
refrigerant using a scale.
CHARGING REFRIGERANT
The R-410A refrigerant is blended. Add only liquid refrigerant.
Measure the quantity of the refrigerant according to the length of the liquid side pipe. Add the quantity of the
refrigerant using a scale.
Summary of Contents for Inuit 6I
Page 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Page 16: ...16 IGLU Inuit 6WTI indoor unit...
Page 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Page 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Page 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Page 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Page 43: ...43...