46
IGLU® Inuit 6I/ IGLU® Inuit 6WTI
When removing the outer cover of the power cable, use the appropriate tools to prevent damaging the inner cover.
Make sure to place the outer cover of the power cable and the communication cable, at least 20 mm into the
electrical parts.
Communication wiring should be done separately from the power cable and other communication cables.
I
GLU® Inuit 9I/ IGLU® Inuit 9WTI
I
GLU® Inuit 12I/ IGLU® Inuit 12WTI
I
GLU® Inuit 16I/ IGLU® Inuit 16WTI
• You should connect the power cable to the power cable terminal and fasten it with a clamp.
• The unbalanced power must be maintained within 2 % of the supply rating.
If the power is greatly unbalanced, it may shorten the life of the condenser. If the unbalanced power is
exceeded over 4 % of the supply rating, the indoor unit is protected, stopped and the error mode indicates.
• To protect the product from water and possible shock, you should keep the power cable and the connection
cord of the indoor and outdoor units within ducts. (With appropriate IP rating and material selection for your
application)
• Ensure that the main supply connection is made through a switch that disconnects all poles, with a contact gap of a
least 3 mm.
• Devices disconnected from the power supply should be completely disconnected in the condition of
overvoltage category.
• Keep distances of 50 mm or more between the power cable and the communication cable.
Summary of Contents for Inuit 6I
Page 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Page 16: ...16 IGLU Inuit 6WTI indoor unit...
Page 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Page 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Page 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Page 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Page 43: ...43...