REFRIGERANT PIPING WORK
Install the refrigerant pipe within the maximum allowable length, the difference in height and length after the first
branch pipe.
The pressure of the R-410A is high.
Use only rated refrigerant pipe and follow the installation method.
Use clean refrigerant pipe where there is no harmful ion, oxide, dust, iron content, or moisture.
Use adequate tools and accessories for R-410A.
Manifold
Use a manifold gauge only for R-410A to prevent the inflow of foreign substances.
Vacuum pump
Use a vacuum pump with a check valve to prevent pump oil from flowing backward while the
vacuum the pump is stopped.
Use the vacuum pump so that the vacuum induction is available up to 5Torr. (-100.7kPa)
Flare nut
Use only the flare nut supplied with the product.
ALLOWABLE LENGTH OF THE REFRIGERANT PIPE AND THE INSTALLATION
EXAMPLES
ITEM
EXAMPLE
REMARKS
The maximum
allowable length
of pipe
Outdoor unit
Total length
Less than 50m
a ≤ 50 m
Maximum
allowable height
Outdoor unit
Less than 30 m
H1
If outdoor unit
is located lower
position H1
≤15 m
Additional refrigerant calculation
R=Basic additional charge by the piping length
Contact the manufacturer if the length should exceed.
Summary of Contents for Inuit 6I
Page 1: ...5 INSTALLATION MANUAL AIR TO WATER HEAT PUMP IGLU INUIT...
Page 16: ...16 IGLU Inuit 6WTI indoor unit...
Page 17: ...17 IGLU Inuit 9I outdoor unit IGLU Inuit 9I indoor unit...
Page 18: ...18 IGLU Inuit 9WTI outdoor unit IGLU Inuit 9WTI indoor unit...
Page 19: ...19 IGLU Inuit 12I IGLU Inuit 16I outdoor unit IGLU Inuit 12I IGLU Inuit indoor unit...
Page 27: ...27 SPACE REQUIREMENTS FOR OUTDOOR UNIT WHEN INSTALLING ONE OUTDOOR UNIT...
Page 43: ...43...