Inclination sensor JN
34
Set point
Measuring method
Minimum
Maximum
Unit
rP2
Vibration measurement 0
15999
1 mg
The set point SP always has to be smaller than the respective reset point rP. Otherwise the sensor
refuses setting of the parameter.
The minimum distance between SP and rP of 1° for inclination measurement or 1 mm/s and 1 mg
for vibration measurement always has to be observed. Otherwise the sensor refuses setting of the
parameter.
If an rP is to be set to a new value which is above the respective SP, SP has to be set to a
considerably higher new value beforehand. Otherwise the sensor refuses setting of the parameter.
Analogously rP has to be adapted before SP is adjusted.
14.6.1 Setting via ISDU indices
The set points SP1 and SP2 as well as the reset points rP1 and rP2 can be set via
ISDU indices depending on the selected measuring method (inclination or vibration
measurement).
Index Sub-
index
Type
Value
Content
Read /
Write
Length
583
0
INT16
SP1 for inclination measurement
Angle X
[1/100 °]
R/W
2
584
0
INT16
rP1 for inclination measurement
Angle X
[1/100 °]
R/W
2
585
0
INT16
SP1 for vibration measurement
veff
[1/10 mm/s]
R/W
2
586
0
INT16
rP for vibration measurement
veff
[1/10 mm/s]
R/W
2
593
0
INT16
SP2 for inclination measurement
Angle Y
[1/100 °]
R/W
2
594
0
INT16
rP2 for inclination measurement
Angle Y
[1/100 °]
R/W
2
595
0
INT16
SP2 for vibration measurement
aPeak [mg]
R/W
2
596
0
INT16
rP2 for vibration measurement
aPeak [mg]
R/W
2
14.7 Teach SP and rP via system commands
The set points SP1 and SP2 as well as the reset points rP1 and rP2 can be set via
IO-Link system commands (ISDU index 2) depending on the selected measuring
method (inclination or vibration measurement).
When the respective system commands are sent, the set and reset points are
adopted according to the current process value.