The measured values are implemented to the voltage intensity on the outputs
as shown in the diagram below. Angle values smaller than the set start point are
constantly mapped to the lowest value of 2 V. Angle values greater than the set
end point are constantly mapped to the highest value of 10 V.
10
2
U [V]
Angle [°]
ASP
e.g. - 60 ° → ASP = -6000
AEP
e.g. + 120 ° → AEP = +12000
13.3 Teach ASP and AEP via system commands
The analogue start points ASP1 and ASP2 as well as the analogue end points
AEP1 and AEP2 can be taught according to the selected measuring method
(inclination or vibration measurement) via IO-Link system commands (ISDU index
2).
When the respective system command is sent, the start and end points are
adopted according to the current process value.
System command
(ISDU index 2)
Action
0xCB
Teach ASP1
0xCC
Teach AEP1
0xCD
Teach ASP2
0xCE
Teach AEP2
When an analogue start or end point has been taught by sending a system command, the new
values for the start or end points should be checked by reading the respective ISDU index.
Only then can it be seen, if teaching was successful or was refused by the sensor due to non-
observance of the rules "ASP < AEP" and "AEP - ASP ≥ minimum distance".