IO-Link master
32
Parameter
Possible values
Description
Vendor ID
0000
hex
��� FFFF
hex
Vendor ID, identification level 1
The vendor ID of the connected IO-Link device
for the respective port can be parameterised via
the level�
The vendor ID can be found in the data sheet of
the IO-Link device�
Device ID
000000
hex
��� FFFFFF
hex
Device ID, identification level 2
The device ID of the connected IO-Link device
for the respective port can be parameterised via
the level�
The device ID can be found in the data sheet of
the IO- Link device�
To check the device ID, a vendor ID check must
be carried out first�
As soon as the content of the vendor ID and/or device ID is not equal to "0", the IO-Link "Type
Compatible" inspection level is activated� Only if the parameterised vendor ID and the device ID
correspond to the information read (in the device), communication with the device is established
(COM state bit of the corresponding port = 1), otherwise this is rejected (IO-Link LED is red)�
Data storage
Data storage
Deactivated
The data storage mechanism is deactivated�
Download only
The parameter data is sent to the device by the
IO-Link master�
In the event of an inconsistency between the
parameter data of the IO-Link device and the
master, the data from the IO-Link master is taken
as default data�
This means that it is possible to exchange the
IO-Link device�
Upload only
The parameter data is sent to the master by the
IO-Link device�
In the event of an inconsistency between the
parameter data of the IO-Link device and the
master, the data from the device is taken as
default data�
This means that it is possible to replace the IO-
Link master�
Download and Upload
The parameter data is saved in both the IO-Link
master and the device�
In the event of an inconsistency between the
parameter data of the IO-Link device or the
master, the data of both devices is used as
default data�
Therefore it is possible to replace the IO-Link
device or the IO-Link master�