IO-Link master
18
– 4 type A ports with an additional digital input
– 4 type B ports with an additional voltage supply
● Connection of IO-Link ports using M12 connectors (A-coded, 5 poles)
● Parameter data storage on the master
● Parameterisable process data width
● Supporting the IOL_CALL function module
● IO-Link specification v1�1
12.3 General features
● Diagnostic and status indicators
● Short-circuit and overload protection of the sensor supply
● IP65/67 protection rating
13 Technical data
General data
Housing material
Pocan
Weight [kg]
0�48
Ambient temperature (operation) [°C]
-25 ���60
Ambient temperature (storage/transport) [°C]
-25���85
Permissible humidity (operation) [%]
5���95
Air pressure (operation) [kPa]
70���106 (up to 3000 m above sea
level)
Air pressure (storage/transport) [kPa]
70���106 (up to 3000 m above sea
level)
Protection rating
IP65 / IP67
Protection class
III, IEC 61140, EN 61140, VDE
0140-1
Connection data
Connection method
M12 connector
Interface ProfiNet
Number
2
Connection method
M12 connector, D-coded
Designation connection point
copper cable
Number of poles
4
Transmission speed [Mbps]
100 (with auto-negotiation)
ProfiNet
Equipment type
ProfiNet Device