Reliable Automatic Sprinkler Co., Inc.,

 103 Fairview Park Drive, Elmsford, New York 10523

Model DH56 Dry (SIN RA1664)
K5.6 (80 metric)
Extended Coverage
Horizontal Sidewall Sprinkler

Bulle

tin 016 December 2021

Bulletin 016 December 2021

For coverages up to 28 feet wide 
and 10 feet long

(1)

.  250 psi (17,2 bar) 

rated.
Features:

1.  Coverage for long and narrow spaces such as hallways, 

corridors, decks and rooms up to 28 feet wide and 10 

feet long (see figure 1).

2.  Deflector to ceiling dimensions are:

4” (102mm) min. to 12” (305mm) max.

3. 

Minimum spacing between sprinklers 16 feet (4.9m).

(1)

4. 

White polyester, black plyester, and ENT finish sprinklers 

are cULus Listed as Corrosion Resistant (not applicable 

to concealed sprinklers).

5.  5.6  K  Factor.
6.  Sprinkler is approved for 

250 psi (17,2 bar) applications.

8.  Quick response  performance.
9. 

½” (13mm) adjustment of escutcheon and cover.

10. Concealed cover plate can prevent the sprinkler from 

being  used  for  unintended  purposes.  No  exposed 

thermal element with the concealed version.

11. Push-on/thread-off sturdy convenient escutcheon for 

recessed and cover for concealed.

12. Factory assembled sprinkler & cup, shipped complete 

with bulb protector for concealed and FP recessed 
versions.

13. Sprinkler & cup assembly and escutcheon or cover are 

separately packaged.

14. 

Available in a variety of plated and painted finishes

Approval Organizations

•  Listed by Underwriters Laboratories Inc. and 

UL certified for Canada (cULus)

Patents

US Patent No. 7,841,418

Products Description

The Model DH56 are quick response extended coverage  

sidewall dry sprinklers for use in light hazard applications.  
The Model DH56 dry sprinkler with SWC cover plate is a 
concealed sprinkler that uses Reliable’s push on/thread off 
sidewall cover. This sprinkler has the cup factory mounted 
and is shipped with a bulb protector that protects the 3mm 
frangible glass bulb during shipping and post installation 

finishing operations. The DH56 can be combined in 
the field with the FP Escutcheon to make a recessed 

dry sprinkler.  The SWC cover plate and FP recessed 

DH56 HSW Concealed

with SWC cover plate

DH56 HSW

DH56 HSW FP Recessed

DH56 HSW/HB

escutcheons have ½” adjustment.  The SWC cover plate 

is attached with 135 & 165 degree solder.  In the event of 

a fire the rising ambient temperature melts the solder and 
the cover plate is ejected away by springs exposing the 

3mm frangible glass bulb.  The use of a 3mm bulb allows 
quick response which enables the sprinkler to apply water 

to a fire sooner than standard response sprinklers of the 

same temperature rating.

Summary of Contents for DH56 HB

Page 1: ...led and FP recessed versions 13 Sprinkler cup assembly and escutcheon or cover are separately packaged 14 Available in a variety of plated and painted finishes Approval Organizations Listed by Underwriters Laboratories Inc and UL certified for Canada cULus Patents US Patent No 7 841 418 Products Description The Model DH56 are quick response extended coverage sidewall dry sprinklers for use in ligh...

Page 2: ...lb and the wrenching boss This wax will not interfere with the operation of the sprinkler and it prevents contaminants from entering the internal portion of the drop nipple The wax must not be removed Application The Model DH56 is a horizontal sidewall dry sprinkler intended for installation in light hazard occupancies in accordance with NFPA 13 These sprinklers are designed to provide fire protec...

Page 3: ...General Installation Instructions Reliable Model DH56 dry sidewall sprinklers may be installed in ductile or malleable cast iron threaded tees or CPVC tees and adapters upon verification that the sprinkler inlet fitting does not interfere with the interior of the fitting see Figure 9 DO NOT install Reliable Model DH56 dry sidewall sprinklers into elbows or couplings welded outlets mechanical tees ...

Page 4: ...tock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers Prior to installation sprinklers should be maintained in their original cartons and packaging until used to minimize the potential for damage to sprinklers that would cause improper operation or non operation Technical Data K Factor Thread Size Temperature Rating Maximum Ambient Temperature S...

Page 5: ...ter Black Polyester 1 Black Polyester Custom Color Polyester 1 Custom Color Polyester Electroless Nickel PTFE 1 Polished Stainless Steel Notes 1 UL Listed as Corrosion Resistant 2 Escutcheons do not carry corrosion resistant listings 3 Base material is 316 stainless steel Model DH56 Dry Sprinkler with Standard Escutcheon A Dim 2 to 48 51mm to 1219mm in 1 4 6mm increments for 1 connections ...

Page 6: ...ester Custom Color Polyester 1 Custom Color Polyester Electroless Nickel PTFE 1 Stainless Steel Notes 1 UL Listed as Corrosion Resistant 2 Escutcheons do not carry corrosion resistant listings 3 Base material is cold rolled steel unless noted Model DH56 Dry Sprinkler with HB Escutcheon A Dim 3 1 2 to 36 89mm to 914mm in 1 4 6mm increments for 1 connections ...

Page 7: ...lectroless Nickel PTFE 2 Stainless Steel Notes 1 Cup for FP Recessed is unfinished galvanized steel except electroless nickel PTFE sprinkler uses a stainless steel cup 2 UL Listed as Corrosion Resistant 3 Escutcheons do not carry corrosion resistant listings 4 Base material is cold rolled steel unless noted Model DH56 Dry Sprinkler with FP Escutcheon A Dim 3 1 2 to 48 89mm to1219mm in 1 4 6mm incr...

Page 8: ...Chrome Bright Chrome Dull Bright Brass Unfinished Bronze Custom Color Notes 1 Cup for SWC Concealed is unfinished galvanized steel 2 Cover plates do not carry corrosion resistant listings Model DH56 Dry Sprinkler with SWC Cover Plate A Dim 3 1 2 to 48 89mm to1219mm in 1 4 6mm increments for 1 connections ...

Page 9: ...Fig 8 9 ...

Page 10: ...10 Fig 9 ...

Page 11: ...11 Fig 11 ...

Page 12: ...ever applicable Products manufactured and distributed by Reliable have been protecting life and property for over 90 years Ordering Information Specify 1 Sprinkler Type select one Model DH56 Dry EC HSW Model DH56 Dry EC HSW HB Model DH56 Dry Recessed EC HSW FP Model DH56 Dry Concealed EC HSW 2 Sprinkler Temperature Rating 3 Sprinkler Finish 4 Cover Plate Escutcheon Finish 5 Length A Dimension face...

Reviews: