UK
IO-Link master
21
Input voltage range "1" signal [V]
15���30 DC
Input filter time [µs]
< 1000
Overload protection, short-circuit protection of the outputs
electronic
Electrical isolation / isolation of the voltage areas
Test section
Test voltage
24 V supply (communications power and sensor supply, IO-Link
ports) / bus connection (Ethernet 1) [V]
500 AC, 50 Hz, 1 min
24 V supply (communications power and sensor supply, IO-Link
ports) / bus connection (Ethernet 2) [V]
500 AC, 50 Hz, 1 min
24 V supply (communications power and sensor supply, IO-Link
ports) / FE [V]
500 AC, 50 Hz, 1 min
Bus connection (Ethernet 1) / FE [V]
500 AC, 50 Hz, 1 min
Bus connection (Ethernet 2) / FE [V]
500 AC, 50 Hz, 1 min
Bus connection (Ethernet 1) / bus connection (Ethernet 2) [V]
500 AC, 50 Hz, 1 min
24 V supply (actuator supply) /
24 V supply (communications power and sensor supply, IO-Link
ports)
[V]
500 AC, 50 Hz, 1 min
24 V supply (actuator supply) / bus connection (Ethernet 1) [V]
500 AC, 50 Hz, 1 min
24 V supply (actuator supply) / bus connection (Ethernet 2) [V]
500 AC, 50 Hz, 1 min
24 V supply (actuator supply) / FE [V]
500 AC, 50 Hz, 1 min
Mechanical tests
Vibration resistance to EN 60068-2-6/IEC 60068-2-6 [g]
5
Shock to EN 60068-2-27/IEC 60068-2-27 [g]
30, 11 ms period, half-sine shock
pulse
Continuous shock to EN 60068-2-27/IEC 60068-2-27 [g]
10
Conformance with EMC Directive 2004/108/EC
Noise immunity test to EN 61000-6-2
Electrostatic discharge (ESD) EN 61000-4-2/IEC 61000-4-2
criterion B; 6 kV contact discharge;
8 kV air discharge
Electromagnetic fields EN 61000-4-3/IEC 61000-4-3
criterion A; field intensity: 10 V/m
Fast transients (burst) EN 61000-4-4/IEC 61000-4-4
criterion B, 2 kV
Transient surge voltage (surge) EN 61000-4-5/IEC 61000-4-5
criterion B; DC supply lines:
±0�5 kV / ±0�5 kV (symmetrical/
asymmetrical)
Conducted interference EN 61000-4-6/IEC 61000-4-6
criterion A; test voltage 10 V
Noise emission test to EN 61000-6-4
Radio interference properties EN 55022
class A
Approvals
see www�ifm�com