IO-Link master
20
Sensor current [mA]
max� 200 for each channel from
L+/L-
Total current consumption [mA]
max� 1�6 from L+/L-
Input voltage range "0" signal [V]
-3���5 DC
Input voltage range "1" signal [V]
15���30 DC
Input filter time [µs]
< 1000
Overload protection, short-circuit protection of sensor supply
electronic
IO-Link ports in the digital output mode (DO)
Maximum number of outputs
8
Connection method
M12 connector, X01 ��� X04 with
two configurations
Connection method
2, 3 wires
Nominal output voltage [V]
24 DC
Output current for each channel [mA]
200
Output current for each device [A]
1�6
Nominal load, ohmic [W]
12 (48 Ω; with nominal voltage)
Nominal load, inductive [VA]
12 (1.2 H; 12 Ω; with nominal
voltage
Signal delay [µs]
max� 150 (at power on)
Signal delay [µs]
max� 200 (at power off)
Switching frequency
max� 5500 / s (with load current)
Switching frequency
max� 1 / s (with inductive load)
Limitation of the voltage induced on circuit interruption [V]
-15 DC
Max� output voltage when switched off [V]
1
Max� output current when switched off [µA]
300
Behaviour with overload
switched off with auto restart
Overload protection, short-circuit protection of the outputs
electronic
Permissible cable length to the sensor [m]
< 20
Digital inputs on pin 2 for type A ports
Number of inputs
4 (EN 61131-2 type 1)
Connection method
M12 connector, X01 ��� X04 with
two configurations
Connection method
2, 3 wires
Nominal input voltage [V]
24 DC
Nominal input current [mA]
typ� 3
Sensor current [mA]
max� 200 for each channel from
L+/L-
Total current consumption [mA]
max� 1�6 from L+/L-
Input voltage range "0" signal [V]
-3���5 DC