UK
CabinetModule CR2016
13
Parameters
Index in
object
directory
Default value (factory
preset)
Change saved
automatically
Change
effective
Event Timer Tx PDO 1
1800 05
0x00
adjustable
immediately
COB-ID Tx PDO 2
1801 01
0x280 + node ID
adjustable
after PreOp
Trans Type Tx PDO 2
1801 02
0x01 (synchronous)
adjustable
immediately
Inhibit Timer Tx PDO 2
1801 03
0x0000
adjustable
immediately
Event Timer Tx PDO 2
1801 05
0x00
adjustable
immediately
The life time factor 0 is interpreted as 1�The first guard protocol is interpreted as
"start guarding” even if guarding is not yet active at that time (guard time = 0)�
8.4 Manufacturer-specific profiles; Idx 2000 to 5FFF
Parameters
Index in object
directory
Default value
(factory preset)
Change saved
automatically
Change effective
I/O configuration
2000
binary: 12 IN / 16
OUT
analogue:: 4 IN
(0���10V)
adjustable
after PreOp
PWM frequency
2001
0x64 (100 Hz)
adjustable
after PreOp
Node-ID
*)
20F0, 20F1
0x20 (0d32)
yes
after a reset
Baud rate
*)
20F2, 20F3
0x04 (125 Kbit/s)
yes
after a reset
Autostart
20F4
0x00 (off)
adjustable
immediately
*)
Observe rotary switch position!
Entries in the object directory indexes 20F0/20F1 and/or 20F2/20F3 are only valid if the rotary switches for
baud rate and/or node ID are in the position ”F”�
(Position and coding of the rotary switches →
Explanation of the abbreviations:
0x��� = hexadecimal value
0d��� = decimal value
str = string
rw = read-write
ro = read only
u8 = unsigned 8 bits
u16 = unsigned 16 bits