SmartPLC DataLine with Profinet device interface
138
>
Slot 3 – Digital inputs/outputs of B slaves, AS-i master 1
41619
Slot
Description
Value range
Length
[bytes]
3
Digital inputs/outputs of B slaves,
connected to AS-i master 1
B-
slaves 01…07AS-i 1 = B slaves 1 to 7 of AS-i Master 1
4
B-
slaves 01…15AS-i 1 = B slaves 1 to 15 of AS-i Master 1
8
B-
slaves 01…23AS-i 1 = B slaves 1 to 23 of AS-i Master 1
12
all B slavesAS-i 1 = all B slaves of AS-i Master 1
16
In each 4-byte data block, the data of 8 AS-i slaves is transmitted (
→
Mapping of the digital input/output
data
(
>
Slot 4 – Digital inputs/outputs of B slaves, AS-i master 2
41636
Slot
Description
Value range
Length
[bytes]
4
Digital inputs/outputs of B slaves,
connected to AS-i master 2
(only available for devices with 2
AS-i masters)
B-
slaves 01…07AS-i 2 = B slaves 1 to 7 of AS-i Master 2
4
B-
slaves 01…15AS-i 2 = B slaves 1 to 15 of AS-i Master 2
8
B-
slaves 01…23AS-i 2 = B slaves 1 to 23 of AS-i Master 2
12
all B slavesAS-i 2 = all B slaves of AS-i Master 2
16
In each 4-byte data block, the data of 8 AS-i slaves is transmitted (
→
Mapping of the digital input/output
data
(