SmartPLC DataLine with Profinet device interface
41
>
5.3.3
Quick setup: Configure the output access
41783
Only one control instance at a time can have write access to the outputs of the connected AS-i slaves.
The operator configures the control instance with the parameter [Output access].
To configure the control instance of the AS-i slave outputs:
1 Select the menu page
►
►
Select [Operation modes] tab.
2 Set the control instance for the outputs of the AS-i slaves
►
From the list [Output access], select the desired value:
Parameter
Description
Possible values
[Output access]
Control instance of the AS-i
slave outputs
[Gateway]
A higher-level PLC controls the outputs of the
AS-i slaves.
[Manual]
The operator controls the outputs of the AS-i slaves
via the graphical user interface.
[PLC]
The device-internal PLC controls the outputs of the
AS-i slaves.
3 Save the changes
►
Press [Accept selection] to save the changes.
>
The selected instance controls the outputs of the AS-i slaves.