SmartPLC DataLine with Profinet device interface
148
>
Slot 1ss/2ss – flex modules for analogue slaves
41617
In the PROFINET-projection software, every single analogue input/output slave can be shown as
separate slot. Here, the following areas apply:
Slot 101...131 for analogue slaves at AS-i Master 1
Slot 201...232 for analogue slaves at AS-i Master 2
In the flex module representation the first digit identifies the AS-i master the analogue slave is
assigned to. The two following digits stand for the address of the analogue AS-i slave.
Example: Slot 223 = AS-i Master 2, analogue slave with address 23
These slots can contain the following modules in any combination you choose:
Module name
Description
slave type
Channel no.
Slave input/output
1 Channel analogue input (single or A slave)
Single or A slave
0
Input
1 Channel analogue input (B slave)
B slave
0
2 Channels analogue input (single or A slave)
Single or A slave
0 + 1
2 Channels analogue input (B slave)
B slave
0 + 1
4 Channels analogue input (single or A&B slave)
Single slave
or:
A slave
B slave
0…3
0 + 1
0 + 1
1 Channel analogue output (single or A slave)
single or A slave
0
Output
1 Channel analogue output (B slave)
B slave
0
2 Channels analogue output (single or A slave)
Single or A slave
0 + 1
2 Channels analogue output (B slave)
B slave
0 + 1
4 Channels analogue output (single or A&B slave)
Single slave
or:
A slave
B slave
0…3
0 + 1
0 + 1
1 Channel bidirectional analogue (single or A slave)
Single or A slave
0
Input and output
1 Channel bidirectional analogue (B slave)
B slave
0
2 Channels bidirectional analogue (single or A slave)
single or A slave
0 + 1
2 Channels bidirectional analogue (B slave)
B slave
0 + 1
4 Channels bidirectional analogue (single or A&B slave)
Single slave
or:
A slave
B slave
0…3
0 + 1
0 + 1