30
IDS X-Series Training v2.7
Location 14: Global Options
Location Type: Bitmap
These options are global to the alarm system and affect all partitions.
LED Default
Action
Description
1
ON
Cancel the siren
This will allow any user from any partition to enter their code to stop the siren.
2
OFF
Keypad trouble
beep
When this option is enabled and the system detects a trouble condition, the
keypad will beep intermittently to alert the users.
3
OFF
Telephone line
monitoring
This will look for the telephone line voltage and if the telephone line voltage goes
missing a trouble condition will be logged and if another form of communication
is available this will be communicated if option 3 is enabled in location 571.
4
OFF
Keypad beep on
communication
Whenever the alarm successfully communicates via telephone, the keypad will
beep to indicate a successful transfer of information.
5
ON
Keypad Fire,
Medical and
Panic keys
The keypad has an F for fire, M for medical and P for panic keys and this option
enables or disables these keys.
6
ON
Display of
bypassed zones
when armed
When the alarm is armed and this option is enabled, the keypad will display all
zones that have been bypassed. If disabled then none will be shown. This
includes Stay Zones.
7
OFF
Siren delay
This will delay any sound coming from the siren for a period entered into location
18. The alarm will still communicate instantly.
8
ON
Box tamper
monitoring
If you have a switch on the alarm panel housing so that if anyone opens the
housing and the switch is triggered, the panel will log an event and send a
tamper signal if option 8 in location 571.
9
ON
Siren tamper
monitoring
This looks for a load on the siren port, if the load goes missing then a tamper is
triggered and logged. If option 4 in location 571 is enabled a tamper will be sent
to the monitoring company.
10
OFF
Peripheral tamper
monitoring
For monitoring tampering on other devices on the systems keypad bus. If option
1 in location 572 is enabled a message will be sent to the monitoring station.
11
OFF
Onboard
dedicated panic–
silent
On the panel next to zone 8 there is a panic zone. If a silent panic is required
enable this option.
12
ON
Low battery
monitoring
This option will allow the panel to test the battery every 30 min. If the battery is
faulty or low, an event will be logged and with option 8 in location 572 enabled,
a signal will be sent to the control room.
13
ON
Low battery cut
out
This option enables the alarm system to monitor the battery voltage and when it
reaches 10.5V it will shut the system down. When AC is restored the alarm will
switch back on and begin to charge the battery.
14
OFF
Bypassing with
user code
If the area that is being protected is a high security area this forces a user to
insert their code before zones can be bypassed.
15
OFF
Dedicated panic
bypass
This option will allow users to bypass the dedicated onboard panic zone. The
panic zone is bypassed using zone number 65.
16
OFF
Cancel panic via
a remote Tx
If a panic has been triggered this option will allow or deny panic violations to be
reset via the arm/disarm button on the remote Tx. If off only a user code entered
on a keypad will cancel the panic condition.
Location 15: AC Fail / Restore Reporting
Location Type: Standard
This is the time the system waits before reporting that the electricity has been disconnected.
Data format: HHmm
Valid Range: 0001 - 1800
Default: 0004
Note: AC restoral waits for one minute, after AC has been restored before reporting the restoral.