IDS X-Series Training v2.7
Zone Properties
Location 101 to 164: Setting Zone Properties
Location Type: Bitmap
Note: Zone properties are individually setup for each zone.
Option
Default
Description
Explanation
1
OFF
Tamper
This option allows the monitoring of devices, even when the alarm
is not active, for any interference. Note: requires double end of line
resistors
.
2
OFF
Cross-zone
This is when the device has to be triggered a predetermined
number of times within a set time period before the alarm will be
activated. Also known as double knock. (I.e. The zone must trigger
twice in 20 seconds.)
3
OFF
Shutdown Zone
This option monitors the zone for violations and if the set number
of violations is reached whilst the alarm is on, the zone will be
bypassed. (There is an option to try and re-enable the zone when
the alarm does its auto test, if the zone is not violated, under extra
partition options. Locations 221 to 228.)
4
OFF
Silent Zone
This will not set off an audible alarm, (siren) but will report an alarm
activation if the alarm has been configured to do so.
5
OFF
Chime Zone
This will cause the keypad to beep 5 times when violated in an
unarmed state. This can also be done via the user menu.
6
ON
Zone Bypass-able
Enable or disable the zone from being bypassed.
7
OFF
PGM Always Triggers
When enabled this will set the zones PGM outputs (locations 415 -
422) to always trigger when the zone is violated.
9 Profile 1
10 Profile 2
11 Profile 3
12 Profile 4
OFF
Stay Profile
This is to allocate the zone to a stay profile so that if that profile is
activated the zone will be bypassed. A stay profile is used to
deactivate certain zones when the alarm is active, allowing
movement within those zones. Different, or the same zones, can
be allocated to 4 different profiles allowing for different situations
that may arise. (This can also be set via the user menu.)
13 Profile 1
14 Profile 2
15 Profile 3
16 Profile 4
OFF
Buzz Profile
Again this is an option to allocate zones to a buzz profile. A buzz
zone only works in the stay mode, allowing the zone to be violated
for 30 seconds before triggering the alarm. During the 30 seconds,
the keypad will sound the buzzer as an audible warning to alert the
person that the zone has been violated. As with stay profiles,
different or the same zones can be allocated to 4 different profiles
allowing for different situations that may arise. (This can also be set
via the user menu.) Buzz profile 1 is associated with stay profile 1,
etc.
Exercise:
Zone 16 is a panic zone, let’s make it a silent panic so that the siren will not trigger alerting the intruder,
but will send the signal to the monitoring company.
Instructions
Key Presses
Enter location 116
[1][1][6] [*]
Select the silent zone option
[4] [*]
LED 4 will come on
Exit the location
[#]