Chapter 2: Hardware Installation
DIP Switch Settings
The following image and table will show the Relay Box Dip switch and the various settings that may
be used. The DIP switch settings in the table are for normal operations.
The ON position is marked with an arrow and is always up. A 24 Output Relay Box will ship as ADDR1.
If you were to add a second Relay Box to the system, it should be addressed as ADDR9.
Tunnel Master® Jr. AC Power Terminations
Figure 2-19. DIP Switch Settings located on the inside of the Relay
Switch
Default
Setting
Function
1
OFF
Address Setting:
1, 2, 3, 4 OFF
1 ON; 2, 3, 4 OFF
1 ON; 2, 3 OFF; 4 ON
1 ON; 2 Off; 3 ON; 4 OFF
1 ON; 2 OFF; 3, 4 ON
= Address 1
= Address 9
= Address 10
= Address 11
= Address 12
2
OFF
Address Setting:
3
OFF
Address Setting:
4
OFF
Address Setting:
5
OFF
Baud Rate:
OFF = 9600
ON = 38,400
6
OFF
Up position allows access to Initialization Menu options
7
OFF
Pulse
7, 8 OFF
Normal
8
ON
Pulse Enhancement
7 OFF; 8 ON
7 ON; 8 OFF
7, 8 ON
2 Times
4 Times
8 Times
Table 2-4.
DIP Switch Settings