Environment, Operating:
1, 5
High Ambient
Temperature
Long-term recommended
27°C (80.6°F)
4
Maximum ambient allowed
32°C (89.6°F)
4
Low Ambient
Temperature
Long-term recommended
18° (64.4°F)
Minimum ambient allowed
10° (50°F)
Low end humidity
Long-term recommended
5.5°C (41.9°F) dew point
Minimum relative humidity
allowed
8%
High end humidity
Long-term recommended
60% relative humidity and 15°C
(59°F) dew point
Maximum relative humidity
allowed
80% relative humidity and 17°C
(62.6°F) dew point
Gaseous contamination
Class G1 as per ANSI/ISA S71.04–1985
2
Particulate contamination 1. Room air must be filtered continuously using appropriate
filters.
2. The deliquescent relative humidity of the particulate
contamination shall be more than 80%
3
Environment, Nonoperating:
5
Temperature
5°C (45°F) to 41°C (113°F)
Rel Humidity
8% - 80%
Maximum Dew Point
Less than 27°C (80.6°F)
Gaseous contamination
Class G1 as per ANSI/ISA S71.04–1985
2
Environment, shipping:
Temperature
-40°C (-40°F) to 60°C (140°F)
Rel Humidity
5% - 100% (no condensation)
Wet Bulb
Less than 29°C (84.2°F)
Shipping package
IBM-approved vapor barrier bag with desiccant
Environment, storage:
Temperature
1°C (33.8°F) to 60°C (140°F)
Relative Humidity
5% -80% (no condensation)
Wet Bulb
Less than 29°C (84.2°F)
Shipping package
IBM-approved vapor barrier bag with desiccant
Notes:
1. Maximum ambient temperature reduces 1
o
C (1.8
o
F) for every 300 m (984 ft) over 900
m (2953 ft).
2. ANSI/ISA-S71.04. 1985. "Environmental conditions for process measurement and
control systems: Airborne contaminants." Instrument Society of America, Research
Triangle Park, NC, 1985.
3. The deliquescent relative humidity of particulate contamination is the relative humidity at
which dust absorbs enough water to become wet and promote ionic conduction.
4. For ambient temperatures exceeding 25
o
C (77
o
F), the acoustical noise levels of the
system may increase significantly as the speeds of the air moving devices increase. See
“Acoustics” on page 99 for the declared acoustical noise emission levels for the system
under nominal temperature conditions of 23
o
C plus or minus 2
o
C (73.4
o
F plus or minus
3.6
o
F).
5. The machine should be in an environment that satisfies the operating environment
specifications for at least one day before it is powered on.
Level 03c, May 2011
10
z10 BC IMPP
||
|
|
|
|
|
|
|
|
|
|
|
|
||
|
|
|
|
||
|
|
|
|
|
|
||
||
|
|
|
||
||
||
||
||
|
||
||
||
||
|
||
||
||
||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Summary of Contents for Z10 BUISNESS CLASS Z10 BC
Page 2: ......
Page 8: ...Level 03c May 2011 vi z10 BC IMPP...
Page 10: ...Level 03c May 2011 viii z10 BC IMPP...
Page 44: ...Level 03c May 2011 32 z10 BC IMPP...
Page 50: ...Level 03c May 2011 38 z10 BC IMPP...
Page 62: ...Level 03c May 2011 50 z10 BC IMPP...
Page 86: ...LC Duplex Connectors ISC 3 Links ISC 3 Links FC 18 02 ISC 3 Level 03c May 2011 74 z10 BC IMPP...
Page 106: ...Level 03c May 2011 94 z10 BC IMPP...
Page 110: ...Level 03c May 2011 98 z10 BC IMPP...
Page 112: ...Level 03c May 2011 100 z10 BC IMPP...
Page 116: ...Level 03c May 2011 104 z10 BC IMPP...
Page 130: ...Level 03c May 2011 118 z10 BC IMPP...
Page 131: ......
Page 132: ...Level 03c May 2011 Printed in USA GC28 6875 03...