Internal battery feature (FC 3211)
The Internal Battery Feature (IBF), FC 3211, is optional on the z10 BC. In the event
of input power interruption to the system, the internal battery feature will provide
sustained system operation for the times listed in the following table.
Model *
hold-up time (minutes)
CPC drawer, 0 I/O drawer
17
CPC drawer, 1 I/O drawer
13
CPC drawer, 2 I/O drawers
11
CPC drawer, 3 I/O drawers
9
CPC drawer, 4 I/O drawers
7
Notes:
1. The numbers shown are approximate for 70° C, batteries no older than 3 years, and full
N+1 power (both power supplies in operation).
2. Hold-up times are influenced by temperature, battery age, and fault conditions within the
system.
3. * Assumes maximum supported configuration (maximum I/O adapters installed). Actual
hold-up times will be longer for less-than-maximum configurations.
Level 03c, May 2011
Chapter 5. Power requirements
43
Summary of Contents for Z10 BUISNESS CLASS Z10 BC
Page 2: ......
Page 8: ...Level 03c May 2011 vi z10 BC IMPP...
Page 10: ...Level 03c May 2011 viii z10 BC IMPP...
Page 44: ...Level 03c May 2011 32 z10 BC IMPP...
Page 50: ...Level 03c May 2011 38 z10 BC IMPP...
Page 62: ...Level 03c May 2011 50 z10 BC IMPP...
Page 86: ...LC Duplex Connectors ISC 3 Links ISC 3 Links FC 18 02 ISC 3 Level 03c May 2011 74 z10 BC IMPP...
Page 106: ...Level 03c May 2011 94 z10 BC IMPP...
Page 110: ...Level 03c May 2011 98 z10 BC IMPP...
Page 112: ...Level 03c May 2011 100 z10 BC IMPP...
Page 116: ...Level 03c May 2011 104 z10 BC IMPP...
Page 130: ...Level 03c May 2011 118 z10 BC IMPP...
Page 131: ......
Page 132: ...Level 03c May 2011 Printed in USA GC28 6875 03...