Customer circuit breakers (CBs)
The following table shows the maximum circuit breaker ratings based on input
voltage.
Input Voltage Range (V)
System Rated Current (A)
Circuit Breaker
200 - 240V
24A
30 amps
380 - 415V
16A
16 amps
480V
14A
15 amps
It is recommended, for simplicity and ease of upgrades, that the circuit breaker
ratings in this table be used on all power cords for all installations. The actual
power drawn (heat load) by any configuration will not be affected.
Note:
System z server design incorporates Electromagnetic Interference filter
capacitors required to block electrical noise from penetrating the power grid.
A characteristic of filter capacitors, during normal operation, is high leakage
currents. Depending on the server configuration, this leakage current can
reach 350mA (350 milliamps). For most reliable operation,
Ground Fault
Circuit Interrupter (GFCI), Earth Leakage Circuit Breaker (ELCB) or
Residual Current Circuit Breaker (RCCB) type circuit breakers are not
recommended for use with System z servers.
By internal design and
grounding, System z servers are fully certified for safe operation (compliance
with IEC, EN, UL, CSA 60950-1).
However, if leakage detection circuit breakers are required by local electrical
practice,
the breakers should be sized for a leakage current rating not
less than 500mA
in order to reduce the risk of server outage caused by
erroneous and spurious tripping.
Level 03c, May 2011
42
z10 BC IMPP
Summary of Contents for Z10 BUISNESS CLASS Z10 BC
Page 2: ......
Page 8: ...Level 03c May 2011 vi z10 BC IMPP...
Page 10: ...Level 03c May 2011 viii z10 BC IMPP...
Page 44: ...Level 03c May 2011 32 z10 BC IMPP...
Page 50: ...Level 03c May 2011 38 z10 BC IMPP...
Page 62: ...Level 03c May 2011 50 z10 BC IMPP...
Page 86: ...LC Duplex Connectors ISC 3 Links ISC 3 Links FC 18 02 ISC 3 Level 03c May 2011 74 z10 BC IMPP...
Page 106: ...Level 03c May 2011 94 z10 BC IMPP...
Page 110: ...Level 03c May 2011 98 z10 BC IMPP...
Page 112: ...Level 03c May 2011 100 z10 BC IMPP...
Page 116: ...Level 03c May 2011 104 z10 BC IMPP...
Page 130: ...Level 03c May 2011 118 z10 BC IMPP...
Page 131: ......
Page 132: ...Level 03c May 2011 Printed in USA GC28 6875 03...