© Copyright IBM Corporation 2020. Customer Install Guide, PDU
35
i. Make sure that the long mounting brackets are aligned with the outside of
the rack flanges.
j. Align the blank filler panel (
A
) on the outside of the rack flanges, as shown
in
Figure
12
.
k. Attach the filler panel to the rack flanges and then to the long mounting
bracket with two M6 screws (B) per bracket. Use the screws that were
provided with the rack mounting kit.
l. Proceed with step
10
.
9. Secure the long mounting brackets and the blank filler panel (A) to the rack
cabinet by completing the following steps:
a. Adjust the long mounting brackets to fit the depth of the rack cabinet.
b. Tighten the M3 pan-head screws that secure the long mounting brackets
to the PDU.
c. Make sure that the long mounting brackets are aligned with the inside of
the rack flanges.
d. Align the blank filler panel (A) on the outside of the rack flanges.
e. Attach the filler panel to the rack flanges and then to the long mounting
bracket with two M6 screws (B) per bracket. Use screws that were
provided with the rack mounting kit. Ref Figure 12.
Alternate Method: The fillers that are shipped with your Cloud Pak rack
can be reused in place of the filler that is shipped with the PDU for a more
consistent look.
Figure 12. Attaching the brackets and filler panel to the rack
Summary of Contents for 3454-FCE
Page 6: ...Copyright IBM Corporation 2020 Customer Install Guide PDU 6 Safety...
Page 52: ...Copyright IBM Corporation 2020 Customer Install Guide PDU 52 Figure 29 EPO Setup...
Page 67: ...Copyright IBM Corporation 2020 Customer Install Guide PDU 67 Regulatory and Compliance...
Page 74: ...Copyright IBM Corporation 2020 Customer Install Guide PDU 74...