Chapter 4 Unit connection / In
stallation and Wiring
4.3 Wiring method
4-11
ME0394-1A
[CC-Link dedicated cable and cable connector wiring method]
(1) Prepare a CC-Link dedicated cable.
(2) Strip 7mm of insulation from each wire end.
(3) Insert the stripped wiring in the direction of the arrow
in the figure below to the back of
the connector and tighten with a flathead screwdriver.
(4) (
★
in "Connection image" above)
Attach the controller attached terminal resistor (Note 1) between the connectors DA and DB
at the network terminal end only.
* The terminal resistor of the CC-Link master unit is
to be prepared by the customer.
(5) Other CC-Link dedicated cables are wired in the same manner as in (1) to (4).
Point
!
The terminal resistor to be used may differ depending on the CC-Link dedicated cable
type.
Cable FANC-SBH (CC-Link dedicated high-
performance cable): Terminal resistor: 130 Ω
Cable FANC-SB (CC-
Link dedicated cable): Terminal resistor: 110 Ω
(2)
7
mm
CC-Link
dedicated cable
(1)
(4)
Terminal resistor
(3)
Screwdriver
CC-Link
cable connector
(
MSTB2.5/5-STF-5.08AU
)
DA
DB
DG
SLD
FG
"DA" signal line
"DB" signal line
"DG" signal ground
"SLD" shield