Chapter 5 Operation
5.3 I/O Signals
5-15
ME0394-1A
[2] Alarm clear input (RES) PLC output signal
●
When the [RES] signal is turned ON, the currently triggered alarm will be cleared.
●
Alarm clear may not be possible depending on the alarm itself.
Refer to "7.3.2 Troubleshooting for alarm groups" for detail.
[3] Position detection output backward end/forward end (LS0/LS1) PLC input signal
●
The LS signals perform the same operation as an air cylinder automatic switch.
They are not positioning complete signals.
●
The LS signals turn ON when the current ELECYLINDER position is within the detection
range configured at the backward and forward ends.
●
They turn ON when within the detection range regardless of whether the servo is ON or
OFF.
The backward end and forward end
set values' relationship to [LS0]
and [LS1] signals ON is as follows.
In this example, the LS signal
detection range is ±0.10mm.
To adjust the LS signal detection range,
open the [Edit parameters window].
Parameter No.2
[Auto switch LS signal detection range
adjustment] can be used to
make adjustments.
Backward end
0.00mm
Forward end
200.00mm
[LS0 detection range]
-0.10 to 0.10mm
[LS1 detection range]
199.90 to 200.10mm