
Chapter 6 Parameter
6.2
Parameter Details
ME0394-1A
6-2
6.2 Parameter Details
[Operation range adjustment (Parameter No. 1)]
No.
Name
Unit
Input range
Default initial value setting
1
Operation range
adjustment
mm
0 to 9,999.69
Max. Stroke
●
The ELECYLINDER operation range can be adjusted to suit your system.
●
The minimum setting unit is 0.01mm.
●
Set to your desired stroke length.
The controller automatically adds 0.30mm and controls/monitors the
operation range.
Set the operating stroke between 0 and 80mm
by changing [Parameter No.1] to [80.00mm].
Caution
●
Set within the ELECYLINDER movable range.
Setting to a value that exceeds the maximum stroke will result in collision with the
forward side mechanical stopper
●
This may damage the ELECYLINDER, workpiece or peripheral devices.
Configuration example
0.30mm
0.30mm
80.00mm
(Stroke to be used)
Parameter No.1:
80.00mm
Summary of Contents for Rec
Page 2: ......
Page 133: ...Parameter 6 1 Parameter list 6 1 6 2 Parameter Details 6 2 R E C Chapter 6 ...
Page 156: ......
Page 157: ......
Page 158: ......