Chapter 1 Specifications Check
25
1.4.3
Specifications of PROFIBUS-DP Interface
Item
Specification
Communication Protocol
PROFIBUS-DP
Baud Rate
Automatically follows the master
Communication System
Hybrid System (Master-Slave System or Token Passing System)
Number of occupied stations
Refer to 3.4.1 PLC Address Construction by each Operation Mode
MAX. Total Network
Baud Rate
Cable Type
100m
12,000/6,000/3,000kbps
200m
1,500kbps
400m
500kbps
1000m
187.5kbps
Communication Cable Length
1200m
9.6/19.2/93.75kbps
Type A Cable
Communications Cable
STP cable AWG18
Connector
(Note 1)
9-pin female D-sub Connector
Transmission Path Format
Bus/Tree/Star
Note 1 Please prepare a 9-pin male D-sub connector for the cable-end connector.
1.4.4
Specifications of CompoNet Interface
Item
Specification
Communication System
CompoNet dedicated protocol
Communication Type
Remote I/O communication
Baud Rate
Automatically follows the master
Communication Cable Length
Follows CompoNet specifications
Slave Type
Word-Mixed Slave
Available Node Addresses for Setting 0 to 63 (Setting conducted on controller parameter)
Number of occupied channels
Refer to 3.4.1 PLC Address Construction by each Operation Mode
Communications Cable
(Note 1)
Round Cable (JIS C3306, VCTF2-core)
Flat cable I (with no sheathed)
Flat cable II (sheathed)
Connector (Controller Side)
XW7D-PB4-R (Manufactured by OMRON or equivalent)
Note 1 Prepare the communication cable separately.
1.4.5
Specifications of MECHATROLINK-II Interface
Item
Specification
Slave Type
Intelligent I/O
Baud Rate
MECHATROLINK II 10Mbps
Max. Transmittable Distance
50m
Min. Distance between Stations
0.5m
Number of occupied bytes
Refer to 3.4.1 PLC Address Construction by each Operation Mode
Transmission Frequency
1 to 8ms
Data Length
MECHATROLINK II 32 bytes
Settable Node Address Range
61 to 7F [hex.]
Communications Cable
(Note 1)
STP cable with a Shield (characteristic impedance 130
:
)
Connector
Controller Side
DUSB-ARB82-T11A-FA (Manufactured by DDK or equivalent)
Note 1 Prepare the communication cable separately.