![Hydronix Hydro-Control VI Installation Manual Download Page 53](http://html.mh-extra.com/html/hydronix/hydro-control-vi/hydro-control-vi_installation-manual_2192335053.webp)
Hydro-Control VI Installation Guide HD0455 Rev 1.9.0
53
example, if the main water addition is 70 litres and the Admix Enable is set to 50% the Admix
signal will be activated when the added water reaches 35 litres.
The
Admix Amount
parameter is used to set the amount of Admix used in a recipe. This is
only used to display in the Mix Log.
Temperature Correction Settings
Parameter
Units
Default
Range
Temperature Set Point
°C
20
0 – 100 °C
Temperature Coefficient
%M/°C
0
-9.9999 – 9.9999
The temperature correction settings are designed to allow system designers to compensate for
the effects of hot or cold weather on the reactions in the concrete by changing the target
moisture depending on the temperature. To this end, the settings allow the Target to be
changed by the
Temperature Coefficient
in proportion to the difference of the current
temperature from the
Temperature Set Point
. The equation is:
)
int
(
*
arg
arg
perature
CurrentTem
eSetPo
Temperatur
nt
eCoefficie
Temperatur
et
OldT
et
NewT
−
+
=
AUTO Mode Settings
Parameter
Units
Default
Range
Local Auto Control
None
No
Yes/No
Proportional Gain
None
5
-100 – 100
Integral Gain
None
0
-100 – 100
Derivative Gain
None
0
-100 – 100
The
Local Auto Control
parameter sets the recipe to use the local recipe values for the AUTO
Mode loop rather than the parameters entered in the System Parameters section.
The
Proportional, Integral
and
Derivative Gain
parameters control the water valves during
AUTO Mode. They compare the current sensor value with the target and generate a control
signal for the speed of water addition (during the process the speed of water addition is
controlled initially by opening the coarse and fine valve fully and, as the error is reduced, by
closing the coarse valve and varying the pulse rate of the fine valve). Optimising these
parameters is described in the Operators Guide in the chapter ‘Using Moisture Control’.
Summary of Contents for Hydro-Control VI
Page 4: ...4 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 6: ...6 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 8: ...8 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 30: ...Electrical Installation Chapter 3 30 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 54: ...Commissioning Chapter 4 54 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 68: ...System Design Chapter 5 68 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 88: ...Remote Support Chapter 7 88 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 102: ...Document Cross Reference Appendix D 102 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...