![Hydronix Hydro-Control VI Installation Manual Download Page 51](http://html.mh-extra.com/html/hydronix/hydro-control-vi/hydro-control-vi_installation-manual_2192335051.webp)
Hydro-Control VI Installation Guide HD0455 Rev 1.9.0
51
The
Control Method
parameter sets how the main water is added. If this is set to Preset then
the system will add the fixed quantity of water defined as the
Main Water
parameter in the
Water Addition section on page 1 of the recipe. If the method is set to Auto then the water is
added to reach the target defined in
Moisture Target
. If the method is set to Calculation then
the water is added based on a value calculated using the calibration parameters, the
Moisture
Target
and the average reading taken during the Dry Mix phase of the mix cycle.
The
Plus Tolerance
and
Minus Tolerance
parameters are used at the end of the Wet Mix
phase. If the difference between the average moisture value taken at the end of the wet mix
phase and the target value is greater than the Plus Tolerance above the target, or greater than
the Minus Tolerance below the target, then the Mix Too Wet or Mix Too Dry alarms are
triggered. In AUTO Mode the
Minus Tolerance
is also used as a deadband for the target.
Local Auto-Track Settings
Auto-Track is the facility to configure the system to measure the stability or homogeneity of the
mix. If the sensor value is within a certain deviation for a set time, this function allows the mix
time to finish earlier.
Parameter
Units
Default
Range
Initial Mix Enable
None
No
Yes/No
Pre-wet Mix Enable
None
No
Yes/No
Dry Mix Enable
None
No
Yes/No
Wet Mix Enable
None
No
Yes/No
Local Auto-Track Control
None
No
Yes/No
Dry Mix Deviation
%
0.1
0 – 100 %
Dry Mix Time
Seconds
10
0 – 100 s
Wet Mix Deviation
%
0.1
0 – 100 %
Wet Mix Time
Seconds
10
0 – 100 s
Initial Mix Enable, Pre-wet Mix Enable, Dry Mix Enable and Wet Mix Enable parameters
can be used to set whether the auto track feature is used on any of the mix phases .
If the
Local Auto-Track Control
option is set then the Auto-Track parameters defined in the
recipe over-ride the parameters set in the System Parameters.
The
Dry Mix Deviation
,
Dry Mix Time
,
Wet Mix Deviation
and
Wet Mix Time
parameters are
used by the Auto-Track feature to control when the system finishes the dry and wet mix phases.
During the dry or wet mix phase, if the variation in the sensor value is less than the specified
Mix Deviation for the Mix Time then the mixing phase will continue to the next phase.
See the section on Auto-Track on page 66 for more details.
Pressing the Next button
will display the third page of the recipe editor. This has
options for the Calculation Mode Settings and AUTO Mode Settings.
Summary of Contents for Hydro-Control VI
Page 4: ...4 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 6: ...6 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 8: ...8 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 30: ...Electrical Installation Chapter 3 30 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 54: ...Commissioning Chapter 4 54 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 68: ...System Design Chapter 5 68 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 88: ...Remote Support Chapter 7 88 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...
Page 102: ...Document Cross Reference Appendix D 102 Hydro Control VI Installation Guide HD0455 Rev 1 9 0 ...