Unit setup/connection
LVU-CD-40
en(us)
Page 31 / 68
BeWa LVU-CD-40 4035823a en-us 2016-01-08.doc
2016-01-08
Relationships: Remote control/Interval control (with Premium control type
only)
After switching on the LVU, the set interval and the run up time will be
started.
Using the remote control, the motor-pump group can be switched on/off
using the remote control. The timer with the interval and the switch-on time
will continue to run in the background (remote control has priority).
If the motor-pump group is switched off via the remote control, it starts
automatically once the interval is over and runs time controlled via the timer.
If the motor-pump group is switched on via the remote control, it stops once
the interval is over. The timer has priority when switching off.
Thus, the set interval and the switch-on time are not influenced by the remote
control. Instead the timer assumes control again once the interval is over.