Unit setup/connection
LVU-CD-40
en(us)
Page 29 / 68
BeWa LVU-CD-40 4035823a en-us 2016-01-08.doc
2016-01-08
Connecting remote control line (control type standard / premium only)
The unit provides a connection for remote monitoring and a start/stop
function. This lets you monitor, start and stop the unit from a control centre.
Unscrew both screws to the cover (615) for connection. Remove the cover
(615). The description of the connection clamps can be found on the rear.
NOTICE
Incorrect voltage / current at the relay contact
The control will be destroyed.
►
Take note of the maximum voltage and current permitted in the relay
contacts of 24 V DC / 2 A.
►
Only use cables with a cable cross section of > 0.5 mm².
Use a free screw type conduit fitting on the lower side to connect the control
line.
Connect the pilot line and monitoring line to the X3 terminal according to the
following description: