Setting up / installing the unit
OLFCM 15/30/45/60
en(us)
32 / 84
BeWa OLFCM 15-60 3595923a en-us 2018-06-28 .docx
2018-06-28
Check direction of rotation
Check the direction of rotation of the motor by switching it on briefly (jog
mode).
The unit requires a clockwise rotating field at the connecting socket.
NOTICE
Incorrect phase sequence / rotation direction of the motor
The pump will be destroyed.
►
In jog mode, check the direction of rotation of the motors.
►
A rotation direction arrow on the fan cover of the motor identifies the
correct direction of rotation.
If rotation is in the opposite direction, change the phases in the terminal box
or rotate the phases in the connection plug using the phase inverter in the
connection plug.