Status messages – CS1000 (optionally with display)
OLFCM 15/30/45/60
en(us)
66 / 84
BeWa OLFCM 15-60 3595923a en-us 2018-06-28 .docx
2018-06-28
Exceptions Errors
LED
Flash code /
display
CS1000 Status
To do
Error
no.
Analogue output
Switching output
Flow status on the
digital output
OFF
CS
no display
no function.
Check the supply
voltage for the CS.
Contact HYDAC.
-
0 mA / 0 V*
open
-
Red
-
Firmware error
Reset the unit. (To
do this, disconnect
the CS from the
voltage supply) or
contact HYDAC.
-1…-19
4.1 mA / 2.05 V*
open
-
Red
-
Communication
error
Check the wiring.
-20…-39
4.1 mA / 2.05 V*
open
-