NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
5 System Operation and Maintenance
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
89
Alarm
ID
Alarm Name System
Action
Possible Causes
Solution
drive board.
3.
Check the status of the
compressor drive board.
4.
Replace the compressor
drive board or compressor.
218
Comp Drive
Short Period
Alarm
The
compressor
shuts down.
(The alarm
needs to be
manually
cleared.)
The Comp Drive Alarm is
triggered multiple times within
a specified period of time.
Refer to the solution to the
Comp Drive Alarm.
219
Comp Drive
Lock Alarm
The
compressor
shuts down.
One of the OutUnit Input
Overcur Alarm, Comp Drive
Overload Alarm, OutUnit
Power Hardware Fault, and
Comp Start Fail Alarm is raised
six times within one hour.
1.
Check the compressor
status.
2.
Check the connection status
of the compressor and the
drive board.
3.
Check the status of the
compressor drive board.
4.
Replace the compressor
drive board or compressor.
220
Comp
Preheating
Alarm
The
compressor
shuts down.
The compressor preheating
function is started and the
preheating is not complete.
Wait until the unit is preheated
completely.
221
Comp Antifrz
Protect Alarm
The
compressor
shuts down.
(The alarm
needs to be
manually
cleared.)
1.
Refrigerant leaks.
2.
The evaporator coil pipe
temperature sensor displays
an incorrect temperature.
3.
The compressor suction
pressure sensor displays an
incorrect pressure after the
coil pipe temperature sensor
is faulty.
4.
The dryer is blocked.
5.
The EEV is blocked.
6.
The air vent of the indoor
unit is blocked.
7.
The indoor fan rotates
reversely.
1.
Identify and repair the
leaking points, and refill
refrigerant after
maintenance.
2.
Calibrate or replace the
evaporator coil pipe
temperature sensor.
3.
Calibrate or replace the
suction pressure sensor
4.
Maintain or replace the
dryer.
5.
Maintain or replace the
EEV.
6.
Check that the air vent of
the indoor unit is not
blocked.
7.
Check the cable connections
to the indoor fan.
222
Comp Run
Timeout
Alarm
--
The runtime of the compressor
exceeds the preset threshold.
Replace the compressor and
clear the cumulative runtime.
301
EEV Low
Superheat
The
compressor
1.
The EEV is faulty or its step
is incorrect.
1.
Check and replace the EEV.
2.
Check and replace the EEV