4 Power-On Commissioning
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
73
Setting
Item
Description
Setting Principle
Default Value
Start All
the return air
temperature is higher
than
Temp for HT
Start All
, all the smart
cooling products in a
group will start cooling
simultaneously.
change the value.
Temp for
HT Start
All
N/A
You are advised not to
change the value.
31°C
Low Temp
Start All
When it is enabled, if
the return air
temperature is higher
than
Low Temp Start
All
, all the smart
cooling products in a
group will start heating
simultaneously.
You are advised not to
change the value.
Disable
Temp for
LT Start All
N/A
You are advised not to
change the value.
13°C
Step 6
After the setting is complete, tap
to return to the user menu.
----End
4.5 (Optional) Setting Monitor Parameters
Procedure
Step 1
Choose
Comm Setting
from the user menu, and tap
to access the communication
setting screen.
Figure 4-10
Communication setting