NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
3 Installation Guide
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
53
2.
(Optional) Signal cables for the indoor unit
3.
Power cable for the outdoor unit
4.
Signal cable between indoor and outdoor units
5.
(Optional) Teamwork and monitoring Cables
3.11.2 Connecting the Indoor Unit Power Cable
The indoor unit power cable needs to be configured by the customer.
The general power cable of the indoor unit must be reliably secured by a cable clip.
shows how to connect the indoor unit power cable.
Figure 3-34
Connecting the indoor unit power cable
3.11.3 (Optional) Connecting the Indoor Unit Signal Cables
Figure 3-35
Signal terminals
Table 3-7
Signal terminal description
Terminal Silk Screen
Terminal
Recommended Cable
X1.1, X1.2
User-defined signal 1
2 x 0.75 mm
2
X1.3, X1.4
User-defined signal 2
2 x 0.75 mm
2