NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (800 mm Width)
3 Installation Guide
Issue 05 (2019-12-20)
Copyright © Huawei Technologies Co., Ltd.
54
Terminal Silk Screen
Terminal
Recommended Cable
X1.5, X1.6
Flame sensor
2 x 0.75 mm
2
X1.7, X1.8
Remote startup and
shutdown
2 x 0.75 mm
2
X1.9, X1.10
Smoke sensor
2 x 0.75 mm
2
X2.4, X2.5
Water sensor
2 x 0.75 mm
2
X2.1, X2.2, X2.3 (Required) Outdoor unit
communication
3 x 16 AWG
3.11.4 Connecting the Outdoor Unit Power Cable and the Signal
Cable Between Indoor and Outdoor Units
Connect the L, N, and GND wires of the outdoor unit to the L, N, and GND terminals of the
indoor unit. Connect the P, Q, and E wires of the outdoor unit to the X2.1, X2.2, and X2.3
terminals of the indoor unit.
The signal cables of indoor and outdoor units must be shielded cables, and the shielding layer must be
reliably grounded.
Figure 3-36
Connecting the outdoor unit power cable and the signal cable between indoor and
outdoor units
3.11.5 (Optional) Connect Teamwork and Monitoring Cables
Network Cable Pin Definition
Table 3-8
Port Pin for Teamwork and Monitoring
Port
Pin
Signal attribute
Description