5.3 Alarms
After troubleshooting, some alarms need to be cleared manually. Press and hold
for 3
seconds to generate a prompt tone, prompting that they have been eliminated.
Table 5-5
Alarms
Alarm
ID
Alarm Name System
Action
Possible Causes
Solution
101
InFan Drive
Lock Alarm
Turn off all
The InFan Drive Alarm is
triggered multiple times within
a specified period of time.
Refer to the solution to the
InFan Drive Alarm.
102
InFan Drive
Alarm
Turn off all
1.
The indoor fan is blocked.
2.
The air vent of the indoor
unit is blocked.
3.
Cables to the indoor fan are
connected incorrectly.
4.
The indoor fan drive or
indoor fan is damaged.
5.
A power failure occurs and
the equipment is restarted
within a short period of
time.
1.
Check that the indoor fan is
not blocked.
2.
Check that the air vent of
the indoor unit is not
blocked.
3.
Check the fan cable
connections.
4.
Replace the fan drive or
indoor fan.
5.
Do not power on and restart
the equipment immediately
after a power failure occurs.
103
InFan Comm
Interrupt
Alarm
Turn off all
1.
Cables to the indoor fan are
disconnected.
2.
The plug of the indoor fan
module board is loose.
3.
The indoor fan module
board is faulty.
1.
Check the cable connections
to the indoor fan.
2.
Check the plug of the indoor
fan module board.
3.
Replace the indoor fan
module board.
105
InFan Run
Timeout
Alarm
--
The runtime of the indoor fan
exceeds the preset threshold.
Replace the indoor fan and
clear the cumulative runtime.
106
Air Filter Run
Timeout
Alarm
--
The runtime of the air filter
exceeds the preset threshold.
Replace the air filter and clear
the cumulative runtime.
201
Comp
Discharge HP
Alarm
The
compressor
shuts down.
1.
The condenser fins are dirty
or blocked.
2.
The outdoor fan or its drive
is faulty.
3.
The high pressure sensor
cable is not properly
connected.
4.
The high pressure sensor is
1.
Clean the condenser fins.
2.
Maintain or replace the
outdoor fan drive or outdoor
fan.
3.
Check the cable connections
to the high pressure sensor.
4.
Maintain or replace the high
pressure sensor.